Design Considerations For Qd Cable Selection; Table 6: Qd Cable Types / Ordering Options; Table 7: Pv Module Orientations With Iq8D - enphase IQ8D-72-E-US Design Manual

Commercial pv design guide microinverter system
Hide thumbs Also See for IQ8D-72-E-US:
Table of Contents

Advertisement

Model Number
QD-12-10-150
QD-12-20-135
QD-12-42-63
QD-12-RAW-300

Design Considerations for QD Cable Selection

Each IQ8D Microinverter supports two series connected
PV modules and a maximum of 9 Microinverters in a
branch circuit. IQ8D Microinverter system support multiple
positioning and orientation options for PV modules
through multiple QD cable SKUs. Cable pitch/SKU selection
and Microinverter mounting point need to be decided
according to module positioning and orientation on roof.
2 X 9 Module Matrix -
Portrait Layout
1 X 18 Module Matrix -
Landscape Layout
2 X 9 Module
Matrix - Landscape Layout
1 X 18 Module Matrix -
Landscape Ballast Layout
© 2022 Enphase Energy Inc. All rights reserved.
QD CABLE TYPES / ORDERING OPTIONS
Size
Max Voltage
277 VAC
12 AWG
277 VAC
12 AWG
277 VAC
12 AWG
300 m (984�2 ft) of 12 AWG cable with no connectors

Table 6: QD Cable Types / ordering Options

2.4m, ~7.9 feet
J-Box
L1-L2
L2-L3
2.4m, ~7.9 feet
J-Box
L1-L2
L2-L3
J-Box
L1-L2

Table 7: PV Module Orientations with IQ8D

Connector
PV Module Orientation
Spacing
1�4 m (4�6 ft)
2�4 m (7�9 ft)
4�6 m (15�1 ft)
Following are some example around module layout and
cable pitch requirements. Based on module layout
correct able SKU should be selected from Table 6.
1.4m, ~4.6 feet
J-Box
L1-L2
L2-L3
L3-L1
L3-L1
L3-L1
L3-L1
4.6 m, ~15.1 feet
L2-L3
L3-L1
Count per Box
Portrait
Landscape
Landscape Ballast
L1-L2
L2-L3
IQ8D-DG-MKT-00397-02-EN-US-2022-06-10
Connector
150
135
63
Alternate layout
L1-L2
L2-L3
L3-L1
Alternate layout
L1-L2
L2-L3
L3-L1
Alternate layout
L1-L2
L2-L3
L3-L1
Alternate layout
L1-L2
L2-L3
L3-L1
L3-L1
20

Advertisement