F I/O Module Without Ipar Server Functionality; Profisafe Address Set Using The Coding Switch; Profisafe Address Set Using The Parameterization Tool - WAGO 750 Manual

4fdi 24v profisafe
Table of Contents

Advertisement

WAGO I/O System 750
753-661/000-004 4FDI 24V PROFIsafe
When using the WAGO iPar server functionality, follow the procedure found in
the corresponding application note.
9.1.3

F I/O Module without iPar Server Functionality

9.1.3.1

PROFIsafe Address Set Using the Coding Switch

If the PROFIsafe address of the F I/O module to be replaced is set using the
coding switch on the side, i.e., the switch setting does not equal 0, set the
replacement module identically to the F I/O module that was replaced. Then set
the parameters for the replacement I/O module using the WAGO
parameterization tool (see section "Commissioning" > "Parameterization of the
F I/O Module with the WAGO Parameterization Tool").
9.1.3.2

PROFIsafe Address Set Using the Parameterization Tool

If the coding switch of the F I/O module to be replaced is set to 0, the PROFIsafe
address of the replacement module must be set through the WAGO
parameterization tool. After setting the PROFIsafe address, set the parameters
for the replacement I/O module using the WAGO parameterization tool (see
section "Commissioning" > "Parameterization of the F I/O Module with the WAGO
Parameterization Tool").
Determine the PROFIsafe address if the coding switch is set to "0"
You can find the PROFIsafe address of the F I/O module to be replaced in the
system documentation.
Version 1.0.0, valid from HW/SW Version 01/01
Service
99
Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

753-661/000-004

Table of Contents