WAGO 750 Manual page 92

4fdi 24v profisafe
Table of Contents

Advertisement

92
Diagnostics
Table 36: Diagnostic Messages
Message
Overload clock
output
Overtemperature
error
Overtemperature
warning
Overvoltage field
supply
PROFIsafe CRC2
error
Manual
Version 1.0.0, valid from HW/SW Version 01/01
Diagnostic type Channel diagnostics
Coding
0x0286
LED indicator
Channel status: red
Description/
Clock output of the F I/O module is
remedy
overloaded. Check the clock output's
wiring.
Classification
Error
Diagnostic type Module diagnostic
Coding
0x0205
LED indicator
Module error: red
Description/
The permissible internal temperature of
remedy
the enclosure was exceeded, which results
in module-wide passivation of the F I/O
module. Make sure that the surrounding
air temperature is within the specified
range.
Classification
Error
Diagnostic type Module diagnostic
Coding
0x0232
LED indicator
No indicator
Description/
A defined internal enclosure temperature
remedy
was exceeded, which does not result in
module-wide passivation of the F I/O
module. Make sure that the surrounding
air temperature is within the specified
range.
Classification
Warning
Diagnostic type Module diagnostic
Coding
0x0230
LED indicator
Module error: red
Description/
The 24 V field supply of the F I/O module
remedy
is above the specified tolerance. Correct
the power supply responsible.
Classification
Error
Diagnostic type Module diagnostic
Coding
0x004D
LED indicator
Module error: red
PROFIsafe status: red, flashing at 1 Hz
Description/
A CRC2 error occurred during safe
remedy
communication. Check the communication
connection and acknowledge the error
message.
Classification
Error
WAGO I/O System 750
753-661/000-004 4FDI 24V PROFIsafe
Description

Advertisement

Table of Contents
loading

This manual is also suitable for:

753-661/000-004