Protective Door Monitoring Connection, Dual-Channel, Antivalent Pre-Evaluation; Figure 29: Connection 1 × Interlock Monitoring, Dual Channel, Antivalent Pre - WAGO 750 Manual

4fdi 24v profisafe
Table of Contents

Advertisement

WAGO I/O System 750
753-661/000-004 4FDI 24V PROFIsafe
7.5.1.3
Protective Door Monitoring Connection, Dual-Channel, Antivalent
Pre-Evaluation
Figure 29: Connection 1 × Interlock Monitoring, Dual Channel, Antivalent Pre-Evaluation
To monitor protective door devices, you can connect the normally open contacts
of a safety interlock switch to four digital inputs of the F I/O module.
Use the WAGO parameterization tool to set the parameters.
Set the Pre-Evaluation parameter for the digital inputs used to "Antivalent." To
have the signal lines of the digital inputs of the F I/O module monitored for short
circuits, set the Short Circuit Test parameter for all inputs to "Activated." In
addition, set the Discrepancy Time parameter to the discrepancy time required
for the normally open contact of the safety interlock switch.
With this wiring, you can achieve a risk reduction of SIL3/Cat.4/PL e.
2
Functional safety evaluations were carried out by TÜV Rheinland.
Version 1.0.0, valid from HW/SW Version 01/01
Commissioning
81
2
Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

753-661/000-004

Table of Contents