WAGO 750 Manual page 91

4fdi 24v profisafe
Table of Contents

Advertisement

WAGO I/O System 750
753-661/000-004 4FDI 24V PROFIsafe
Table 36: Diagnostic Messages
Message
Invalid
F_Source_Add
Invalid
F_WD_Time
Invalid
iParameters
Non-supported
F_Block_ID
Non-supported
F_SIL
Diagnostic type Module diagnostic
Coding
0x0042
LED indicator
Module error: red
PROFIsafe status: red
Description/
The PROFIsafe address of the safe
remedy
controller must be in the range of 1 ...
65534. Correct the F parameterization.
Classification
Error
Diagnostic type Module diagnostic
Coding
0x0043
LED indicator
Module error: red
PROFIsafe status: red
Description/
The monitoring time for fail-safe data
remedy
exchange must be set to a value greater
than "0 ms." Correct the
F parameterization.
Classification
Error
Diagnostic type Module diagnostic
Coding
0x0200
LED indicator
Module error: red,
Parameterization: red, flashing at 1 Hz
Description/
The iParameter set for the F I/O module is
remedy
invalid. Correct the parameterization,
taking dependencies between individual
settings into account.
Classification
Error
Diagnostic type Module diagnostic
Coding
0x004C
LED indicator
Module error: red
PROFIsafe status: red
Description/
The F parameter block specified by the
remedy
F_Block_ID is not supported by the F I/O
module. Use an F parameter block
supported by the F I/O module.
Classification
Error
Diagnostic type Module diagnostic
Coding
0x0044
LED indicator
Module error: red
PROFIsafe status: red
Description/
The F I/O module cannot be operated in
remedy
the configured safety integrity level (SIL).
Correct the F parameterization.
Classification
Error
Version 1.0.0, valid from HW/SW Version 01/01
Diagnostics
Description
91
Manual