Changing Controller Ip Address - Epson RC700-D Manual

Robot controller
Table of Contents

Advertisement

Functions 7. LAN (Ethernet Communication) Port
Our robot system is provided on the assumption that customers use it in the closed local area
networks. We considered the setting of the global IP address is access to the Internet and
changed the specification to perform password authentication in order to secure the
connections.
Password authentication is not performed in case of USB connections.
Be sure to use the following private IP addresses.
The following is the configuration of the Controller at delivery.
IP Address :
IP Mask
IP Gateway
Set separate IP addresses in the same subnet for PC and the Controller.
PC
Controller : 192.168.0.1

7.3 Changing Controller IP Address

This section describes the procedure to change the Controller IP address.
(1) Connect between the development PC and the Controller using the USB cable by
(2) Select the EPSON RC+ 7.0 menu-[Setup]-[Controller] to display the following dialog.
(3) Select [Controller]-[Configuration].
(4) Enter the proper IP address and subnet mask and click the <Apply> button.
(5) Click the <Close> button. The Controller reboots automatically.
104
Private Address List
10.0.0.1
to
10.255.255.254
172.16.0.1
to
172.31.255.254
192.168.0.1
to
192.168.255.254
192.168.0.1
:
255.255.255.0
: 0.0.0.0
: 192.168.0.10
referring to 5. Development PC Connection USB Port.
IP address configuration is completed and the Controller reboot dialog disappears.
RC700-D Rev.2