Energy Management

5.2 Energy Freeze

5.2
Energy Freeze

Function Description

5.2.1
The function of Energy Freeze is used to configure the freezing interval for the energy values. After a time
interval is configured, the energy values are frozen and not updated during the interval until the next interval
starts. The frozen values are transmitted by the report function and the IEC 61850 protocol in the MMTN/
MMTR logic node.

Configuration and Value View via Web Pages

5.2.2
Configuration of the Energy Freeze
To change the settings of the energy freeze and reset in the Configuration tab, proceed as follows:
In the navigation window, click Energy freeze .
[2021-11-30_144306, 1, en_US]
Figure 5-7
Configure the respective parameters according to the following table.
Table 5-4
Parameter
Interval
After the parameterization, click Send.
In the navigation window, click Activation and cancel.
Enter the activation password (refer to
Click Activation.
Value View of the Frozen Energy
To display the values of the frozen energy in the Value view tab, proceed as follows:
In the navigation window, click Frozen energy.
108
Configuration Tab, Energy Freeze
Settings for Energy Freeze
Default Setting
10 min
Setting Range
10 min, 15 min, 30 min, 60 min
Table
2-3).
SICAM, SICAM P850/P855 7KG85X, Manual