Operational Indications and Operating Parameters
13.3 Advanced Functions
Parameter
2 measured values, numerical:
•
Display 1, numerical
•
Display 2, numerical
4 measured values, numerical:
•
Display 1, numerical
•
Display 2, numerical
•
Display 3, numerical
•
Display 4, numerical
2 measured values, graphical, and numer-
ical:
•
Display 1, graph./num.
•
Display 2, graph./num.
3 measured values, graphical, and numer-
ical:
•
Display 1, graph./num.
•
Display 2, graph./num.
•
Display 3, graph./num.
Display x, graph./num. (x = 1 to 3)
•
Min value
•
Max value
Energy Management
13.3.4
13.3.4.1
Load Profile
Table 13-18
Parameter
Subperiod time
Number of subperiods
Synchronization source
Kind of used reactive power
27
Number = 1: Fixed Block method: The lengths of the subperiod and of the measuring period are identical; Number = 2 to 5: Rolling
Block method; Length of the subperiod: The length of the subperiod is an integer part of a full hour; Length of measuring period: The
length of the measuring period cannot be configured directly. It is defined as the product of the length of the subperiod and the
number of subperiods: Length of measuring period = n x length of subperiod; n = number of subperiods
272
Settings for Load Profile
Default Setting
15 min
1
27
Internal clock
Q1
Default Setting
Setting Range
-not assigned-
The selection of measured values
depends on the network type.
Designation can be changed during
the parameterization.
-not assigned-
-not assigned-
-not assigned-
Unit according to meas-
The selected parameters are used to
ured value
define the minimum and maximum
values.
1.0
10.0
Setting Range
1 min to 6 min in 1-min steps,
10 min, 12 min, 15 min, 20 min, 30 min, 60 min
1 to 5
None
Protocol
Internal clock
Q1
Qn
Qtot
SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022