Configuration and Value View via Web Pages
Configuring the Frequency Events
[sc_Param frequency events, 1, en_US]
Figure 6-17
To change the frequency event settings in the Configuration tab, proceed as follows:
•
In the navigation window, click Event records
•
Configure the respective parameters according to the following table.
Table 6-10
Parameter
Underfrequency threshold
Overfrequency threshold
•
After the parameterization, click Send.
•
In the navigation window, click Activation and cancel.
•
Enter the activation password (refer to
•
Click Activation.
Value view of the Frequency Events
To display the frequency event values in the Value view tab, proceed as follows:
•
In the navigation window, click Events.
•
Configure the respective parameters according to the following table.
Table 6-11
Parameter
Event record type
Start time
130
Configuration Tab, Frequency Events
Settings for Frequency Events
Default Setting
1 %
1 %
Settings for Viewing the Frequency Events
Default Setting
Frequency event
One hour before the current date/
time
Setting Range
0.1 % to 1.0 %, increments of 0.1 %
1.0 % to 5.0 %, increments of 1.0 %
0.1 % to 1.0 %, increments of 0.1 %
1.0 % to 5.0 %, increments of 1.0 %
Table
2-3).
Setting Range
Voltage event
Frequency event
Voltage unbalance event
You can edit the text box directly or
select the start time from the
calendar.
SICAM, SICAM P850/P855 7KG85X, Manual