Frequency Events; Configuration And Value View Via Web Pages - Siemens SICAM 7KG85X Manual

Table of Contents

Advertisement

Power Quality
6.4 Event Records

Frequency Events

6.4.3
6.4.3.1

Configuration and Value View via Web Pages

Configuring the Frequency Events
[sc_Param frequency events, 1, en_US]
Figure 6-17
To change the frequency event settings in the Configuration tab, proceed as follows:
In the navigation window, click Event records
Configure the respective parameters according to the following table.
Table 6-10
Parameter
Underfrequency threshold
Overfrequency threshold
After the parameterization, click Send.
In the navigation window, click Activation and cancel.
Enter the activation password (refer to
Click Activation.
Value view of the Frequency Events
To display the frequency event values in the Value view tab, proceed as follows:
In the navigation window, click Events.
Configure the respective parameters according to the following table.
Table 6-11
Parameter
Event record type
Start time
130
Configuration Tab, Frequency Events
Settings for Frequency Events
Default Setting
1 %
1 %
Settings for Viewing the Frequency Events
Default Setting
Frequency event
One hour before the current date/
time
Setting Range
0.1 % to 1.0 %, increments of 0.1 %
1.0 % to 5.0 %, increments of 1.0 %
0.1 % to 1.0 %, increments of 0.1 %
1.0 % to 5.0 %, increments of 1.0 %
Table
2-3).
Setting Range
Voltage event
Frequency event
Voltage unbalance event
You can edit the text box directly or
select the start time from the
calendar.
SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sicam p850Sicam p855

Table of Contents