NOTE
i
i
Changing the IP address causes the device to reset and the LEDs signal that the device was started with the
default IP address.
In this case, the parameterized IP address and the default IP address are displayed on the Information tab,
Device information menu item (see
After starting the device with the default IP address, the factory-set passwords are active, too (see
2.2.2 Password

New Device at Initial Commissioning

9.12.3
Basic Configuration
After logging on to the Web page of the device, you must configure the basic functions. For more information,
refer to
2 Basic
9.12.4

Firmware Update at Initial Commissioning

NOTE
i
i
Check the Siemens Internet site whether a new firmware version is available and update your firmware if
necessary.
You can find the manuals and the firmware via the download area in the Siemens Internet under:
http://www.siemens.com/sicam-p850
http://www.siemens.com/sicam-p855
You can find more detailed information on the firmware update in chapter
Pages.
9.12.5

Import and Export of the Configuration File

When configuring many devices, you can export the configuration from 1 device and import it into the other
devices.
Export of the Configuration
You can save both the active and the passive configuration to a file in the Configuration tab. Proceed as
follows:
In the navigation window, click Save Configuration to File.
SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022
9.11.2.8 Starting the Web Page during
Management).
Functions.
Commissioning and First Steps
9.12 Commissioning
Operation).
8.3.2 Firmware Upload via Web
229