4.2

Group Indications

Function Description

4.2.1
Up to 4 Group indications can be parameterized and each of them can be assigned to up to 4 logically linked
single-point indications. The single-point indications can be inverted.
Rule for Linking Indications to a Group Indication
In a group indication, up to 4 indications can sequentially be linked logically. The indications 1 to 4 are always
linked successively as follows:
Indication 1 with Indication 2 = Indication 1/2
Indication 1/2 with Indication 3 = Indication 1/2/3
Indication 1/2/3 with Indication 4 = Group indication
[sc_q200_regular_4x_1, 2, en_US]
[dw_q200_regular_4x_1, 1, en_US]
Figure 4-5
[sc_q200_regular_2x_1, 2, en_US]
SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022
Example: Linking 4 Indications to a Group Indication
Automation Functions
4.2 Group Indications
95