Process Connections
3.2 Binary Outputs
•
After the parameterization, click Send.
•
In the navigation window, click Activation and cancel.
•
Enter the activation password (refer to
•
Click Activation.
Behavior when Activating the Set of Parameters after the Set of Parameters was Changed
Persistent: The binary output is set to the new status (ON or OFF) as defined by the current indication.
Pulse: If the binary output is ON in pulse mode while activating the parameter set, the binary output is imme-
diately switched to OFF after the parameter set has been activated. This happens even if the parameterized
Output time for pulse operating mode has not yet elapsed.
Value View of the Binary Outputs
To display the values of the binary outputs in the Value view tab, proceed as follows:
•
In the navigation window, click Binary outputs.
[sc_value_view_BO, 1, en_US]
Figure 3-6
Depending on the parameterized source type, the indications routed to the binary outputs and energy coun-
ters are evaluated.
3.2.3
Value View via Display
Submenu Binary Outputs
[dw_submenu_binary_outputs, 1, en_US]
Figure 3-7
88
Value View Tab, Binary Status (Binary Outputs)
Submenu Binary Outputs
Table
2-3).