Configure the respective parameters according to the following table.
Table 5-2
Parameter
Subperiod time
Number of subperiods
Synchronization source
Kind of used reactive power
NOTE
i
i
Changing the number and length of the subperiods deletes the load-profile buffer.
•
After the parameterization, click Send.
•
In the navigation window, click Activation and cancel.
•
Enter the activation password (refer to
•
Click Activation.
Value View of the Load Profile
To display the values of the load profile in the Value view tab, proceed as follows:
•
In the navigation window, click Load profiles.
In the decimal separator, you can select whether you want to display the load-profile data with comma or
decimal point after the download.
9
Number = 1: Fixed Block method: The lengths of the subperiod and of the measuring period are identical; Number = 2 to 5: Rolling
Block method; Length of the subperiod: The length of the subperiod is an integer part of a full hour; Length of measuring period: The
length of the measuring period cannot be configured directly. It is defined as the product of the length of the subperiod and the
number of subperiods: Length of measuring period = n x length of subperiod; n = number of subperiods
SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022
Configuration Tab, Load Profile
Settings for Load Profile
Default Setting
15 min
9
1
Internal clock
Q1
Setting Range
1 min to 6 min in 1-min steps,
10 min, 12 min, 15 min, 20 min, 30 min, 60 min
1 to 5
None
Protocol
Internal clock
Q1
Qn
Qtot
Table
2-3).
Energy Management
5.1 Load Profile