Basic Functions
2.6 Ethernet Communication
2.6.3.2
Configuration via Web Pages
Configuration of the IEC 61850 Protocol
To change the IEC 61850 settings in the Configuration tab, proceed as follows:
In the navigation window, click Communication Ethernet.
Select IEC 61850 as the Bus protocol.
[sc_communication_IEC_61850, 1, en_US]
Figure 2-31
Configure the respective parameters according to the following table.
Table 2-20
Parameter
IED Name
Voltage - Dead band
Current - Dead band
Power - Dead band
Power factor - Dead band
70
Configuration Tab, IEC 61850 Settings
Settings for IEC 61850
Default Setting
SICAM_P850/P855_01
5 %
5 %
5 %
5 %
Setting Range
Any, max. 60 characters
Only a-z, A-Z, _, 0-9 are permitted.
The first character must be an alpha character.
1 % to 5 %, in 1 % steps
1 % to 5 %, in 1 % steps
1 % to 5 %, in 1 % steps
2 % to 5 %, in 1 % steps