Parameter
Keep alive time
Communication supervision
time
NOTE
i
i
The 2 port numbers must be different from each other.
After the parameterization, click Send.
In the navigation window, click Activation and cancel.
Enter the activation password (refer to
Click Activation.
Number of Connections (not configurable)
Up to 5 TCP connections are possible:
Without user-defined port 1: 4 connections via the standard port 502
With user-defined port 1: 2 connections via the standard pot 502 and 2 connections via the configured
port number
2.6.2.2

Configuration via Display

Submenu Modbus TCP Settings
The operation is carried out with the softkeys F1 to F4.
[dw_p85x_display_communication_Modbus_TCP, 1, en_US]
Figure 2-29
2.6.2.3

Diagnosis of the Modbus TCP

The diagnosis for the Modbus TCP allows analyzing parameters and communication as well as resetting the
diagnostic counters.
NOTE
i
i
The diagnostic data of Modbus TCP are displayed only if the bus protocol has been selected in the tab
Configuration → Basic configuration → Communication Ethernet.
If the protocol has not been selected, the Diagnosis Modbus TCP window displays -none-.
For the diagnosis of the protocol Modbus TCP in the Maintenance tab, proceed as follows:
In the navigation window, click Modbus.
The Modbus window opens and the Modbus TCP protocol is displayed. For Modbus TCP the Standard
server, the User-port server and the Connection data are analyzed.
SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022
Default Setting
10 s
600 (* 100 ms)
Submenu Communication via Modbus TCP
Setting Range
0 s = switch off
1 s to 65 535 s
0 s = none
100 ms to 6 553 400 ms
Table
2-3).
Basic Functions
2.6 Ethernet Communication