Parameter
Keep alive time
Communication supervision
time
NOTE
i
i
The 2 port numbers must be different from each other.
•
After the parameterization, click Send.
•
In the navigation window, click Activation and cancel.
•
Enter the activation password (refer to
•
Click Activation.
Number of Connections (not configurable)
Up to 5 TCP connections are possible:
•
Without user-defined port 1: 4 connections via the standard port 502
•
With user-defined port 1: 2 connections via the standard pot 502 and 2 connections via the configured
port number
2.6.2.2
Configuration via Display
Submenu Modbus TCP Settings
The operation is carried out with the softkeys F1 to F4.
[dw_p85x_display_communication_Modbus_TCP, 1, en_US]
Figure 2-29
2.6.2.3
Diagnosis of the Modbus TCP
The diagnosis for the Modbus TCP allows analyzing parameters and communication as well as resetting the
diagnostic counters.
NOTE
i
i
The diagnostic data of Modbus TCP are displayed only if the bus protocol has been selected in the tab
Configuration → Basic configuration → Communication Ethernet.
If the protocol has not been selected, the Diagnosis Modbus TCP window displays -none-.
For the diagnosis of the protocol Modbus TCP in the Maintenance tab, proceed as follows:
•
In the navigation window, click Modbus.
The Modbus window opens and the Modbus TCP protocol is displayed. For Modbus TCP the Standard
server, the User-port server and the Connection data are analyzed.
SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022
Default Setting
10 s
600 (* 100 ms)
Submenu Communication via Modbus TCP
Setting Range
0 s = switch off
1 s to 65 535 s
0 s = none
100 ms to 6 553 400 ms
Table
2-3).
Basic Functions
2.6 Ethernet Communication
67