Binary Outputs
Function Description
3.2.1
The device has 2 binary outputs.
Binary outputs are issued as indications.
4 Operating modes are possible:
•
Persistent
•
Persistent with fail safe
•
Pulse
•
Pulse with retrigger
Persistent
The binary output has the status ON or OFF. If the indication becomes invalid, the binary output continues to
maintain its current status.
[dw_persistent, 1, en_US]
Figure 3-1
Persistent with Fail Safe
If the indication becomes invalid, the binary output switches into the OFF state if Source inverted = no, or it
switches into the ON state if Source inverted = yes.
[dw_persistent-with-fail-save, 1, en_US]
Figure 3-2
SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022
Persistent
Persistent with Fail Safe
Process Connections
3.2 Binary Outputs