Basic Functions
2.6 Ethernet Communication
[sc_q100_communication ethernet, 3, en_US]
Figure 2-26
•
Configure the respective parameters according to the following table.
Table 2-18
Parameter
Communication Ethernet
4
IP address
Subnet mask
4
Default gateway
Ethernet switch on
Enable SNMP
Bus protocol
•
After the parameterization, click Send.
•
In the navigation window, click Activation and cancel.
•
Enter the activation password (refer to
•
Click Activation.
2.6.1.3
Configuration via Display
Submenu Ethernet Settings
The operation is carried out with the softkeys F1 to F4.
4
After the parameter changes have been enabled, the device will restart.
64
Configuration Tab, Ethernet Settings
Settings for Communication Ethernet
Default Setting
192.168.0.55
255.255.255.0
192.168.0.1
4
No
No
Modbus TCP
Table
2-3).
Setting Range
Any
0.0.0.0 = DHCP
Any
Any
No
Yes
No
Yes
-None-
Modbus TCP
IEC 61850
SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022