Table 6-23
Parameter
General Information
Company:
Department:
Supervisor:
Inspector:
Location:
Comment:
Power Quality Report
Evaluation mode according to
Flagging acc. to IEC 61000-4-30
Power frequency
Power supply voltage magnitude 95 % of the measurement should be
Flicker severity
Total harmonic distortion (THDS) 95 % of the measurement should be less
Voltage event interruptions
Harmonic
voltages for the
template of EN
50160 LV&MV
Harmonic
voltages for the
template of EN
50160 HV
After the parameterization, click Send.
In the navigation window, click Activation and cancel.
Enter the activation password (refer to
Click Activation.
16
Short for "under consideration"
SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022
Settings for EN 50160 Report
Default Setting
EN 50160 LV&MV
No
99.5 % of the measurement should be
within a deviation of -1.0 % to 1.0 %
100 % of the measurement should be
within a deviation of -6.0 % to 4.0 %
within a deviation of -10.0 % to 10.0 %
100 % of the measurement should be
within a deviation of -15.0 % to 10.0 %
95 % of the measurement should be less
than 1.0 %
than 8.0 %
Short interruption until 1-second duration
Short interruption until 3-minute duration
Long interruption longer than 3-minute
duration
Odd
H3: 5.0, H5: 6.0, H7: 5.0, H9: 1.5, H11:
harmonics
3.5, H13: 3.0, H15: 0.5, H17: 2.0, H19:
1.5, H21: 0.5, H23: 1.5, H25: 1.5
Even
H2: 2.0, H4: 1.0, H6: 0.5, H8: 0.5, H10:
harmonics
0.5, H12: 0.5, H14: 0.5, H16: 0.5, H18:
0.5, H20: 0.5, H22: 0.5, H24: 0.5
Odd
H3: 3.0, H5: 5.0, H7: 4.0, H9: 1.3, H11:
harmonics
3.0, H13: 2.5, H15: 0.5, H17: u.c.
u.c., H21: 0.5, H23: u.c., H25: u.c.
Even
H2: 1.9, H4: 1.0, H6: 0.5, H8: 0.5, H10:
harmonics
0.5, H12: 0.5, H14: 0.5, H16: 0.5, H18:
0.5, H20: 0.5, H22: 0.5, H24: 0.5
16
, H19:
Table
2-3).
Power Quality
6.8 EN 50160 Report
Setting Options
Any text displayed in the
printout of the power-quality
report
Max. 32 characters
EN 50160 LV&MV
EN 50160 HV
User-defined
No
Yes
The settings are fixed for the
template of EN 50160 LV&MV
and EN 50160 HV.
You can edit the limiting
values in the text box directly
under the user-defined evalua-
tion mode.
149