Table 6-23
Parameter
General Information
Company:
Department:
Supervisor:
Inspector:
Location:
Comment:
Power Quality Report
Evaluation mode according to
Flagging acc. to IEC 61000-4-30
Power frequency
Power supply voltage magnitude 95 % of the measurement should be
Flicker severity
Total harmonic distortion (THDS) 95 % of the measurement should be less
Voltage event interruptions
Harmonic
voltages for the
template of EN
50160 LV&MV
Harmonic
voltages for the
template of EN
50160 HV
•
After the parameterization, click Send.
•
In the navigation window, click Activation and cancel.
•
Enter the activation password (refer to
•
Click Activation.
16
Short for "under consideration"
SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022
Settings for EN 50160 Report
Default Setting
–
EN 50160 LV&MV
No
99.5 % of the measurement should be
within a deviation of -1.0 % to 1.0 %
100 % of the measurement should be
within a deviation of -6.0 % to 4.0 %
within a deviation of -10.0 % to 10.0 %
100 % of the measurement should be
within a deviation of -15.0 % to 10.0 %
95 % of the measurement should be less
than 1.0 %
than 8.0 %
Short interruption until 1-second duration
Short interruption until 3-minute duration
Long interruption longer than 3-minute
duration
Odd
H3: 5.0, H5: 6.0, H7: 5.0, H9: 1.5, H11:
harmonics
3.5, H13: 3.0, H15: 0.5, H17: 2.0, H19:
1.5, H21: 0.5, H23: 1.5, H25: 1.5
Even
H2: 2.0, H4: 1.0, H6: 0.5, H8: 0.5, H10:
harmonics
0.5, H12: 0.5, H14: 0.5, H16: 0.5, H18:
0.5, H20: 0.5, H22: 0.5, H24: 0.5
Odd
H3: 3.0, H5: 5.0, H7: 4.0, H9: 1.3, H11:
harmonics
3.0, H13: 2.5, H15: 0.5, H17: u.c.
u.c., H21: 0.5, H23: u.c., H25: u.c.
Even
H2: 1.9, H4: 1.0, H6: 0.5, H8: 0.5, H10:
harmonics
0.5, H12: 0.5, H14: 0.5, H16: 0.5, H18:
0.5, H20: 0.5, H22: 0.5, H24: 0.5
16
, H19:
Table
2-3).
Power Quality
6.8 EN 50160 Report
Setting Options
Any text displayed in the
printout of the power-quality
report
Max. 32 characters
•
EN 50160 LV&MV
•
EN 50160 HV
•
User-defined
No
Yes
The settings are fixed for the
template of EN 50160 LV&MV
and EN 50160 HV.
You can edit the limiting
values in the text box directly
under the user-defined evalua-
tion mode.
149