Communication Interfaces - Siemens SICAM 7KG85X Manual

Table of Contents

Advertisement

Inputs for Alternating Current Measurements, Connector Block E - Cat III
Input alternating currents
Rated input current range
Max. input current
Power consumption per input
At 1 A
At 5 A
Further information about the current measuring inputs
Max. rated input voltage
Measuring error (with calibration) at 23 °C ± 1 °C 50
Hz or 60 Hz
Thermal stability
Binary Outputs, Connector Block G - Cat III
Maximum contact voltage
Alternating voltage
Direct voltage
Maximum currents
Maximum continuous contact current
Maximum pulse current for 0.1 s
Further information about the binary outputs
Internal impedance
Admissible switching frequency
Number of switching cycles

Communication Interfaces

12.1.3
Ethernet Interface
Connection
Protocols
Voltage strength
Transmission rate
Cable for 10/100 Base-T
Maximum cable length 10/100 Base-T
SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022
AC 1 A to 5 A (autorange)
AC 10 A
4 mVA
100 mVA
150 V
Typically 0.1 % under reference conditions
10 A continuous
100 A for max. 1 s
230 V
250 V
100 mA
300 mA
35 Ω
10 Hz
Unlimited
RJ45 connector socket
10/100Base-T acc. to IEEE802.3
LED green:
On: Ethernet Link exists
Flashing: Ethernet activity
Off: no connection
LED yellow:
On: 100 Mbit/s
Off: no connection
Refer to
13.2.4.1 Communication Ethernet
DC 700 V
100 Mbit/s
100 Ω to 150 Ω STP, CAT5
100 m, if correctly installed
Technical Data
12.1 Technical Data