[ II Restrictions ]
II Restrictions

[1] System configuration

1. Table of compatible indoor units <PQHY>
The table below summarizes the types of indoor units that are compatible with different types of heat source units.
Heat
Composing units
source
units
P72
-
P96
-
P120
-
P144
-
P168
-
P192
-
P144
P72
P168
P96
P192
P96
P216
P120
P240
P120
P288
P144
P312
P168
P336
P168
P360
P192
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given heat source unit exceeds the capacity of the heat source
unit, the indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a com-
bination of units so that the total capacity of the connected indoor units is at or below the capacity of the heat source unit
whenever possible.
HWE15150
Maximum total capacity
of connectable indoor
units
-
36 - 93
-
48 - 124
-
60 - 156
-
72 - 187
-
84 - 218
-
96 - 249
P72
72 - 187
P72
84 - 218
P96
96 - 249
P96
108 - 280
P120
120 - 312
P144
144 - 374
P144
156- 405
P168
168 - 436
P168
180 - 468
Maximum number
Types of connectable in-
of connectable in-
door units
1 - 15
P06 - P96 models
R410A series indoor units
1 - 20
1 - 26
1 - 31
1 - 36
1 - 41
1 - 31
1 - 36
1 - 41
2 - 46
2 - 50
- 17 -