System Configuration - Mitsubishi Electric CMB-WM108V-AA Service Handbook

Hide thumbs Also See for CMB-WM108V-AA:
Table of Contents

Advertisement

[ II Restrictions ]
II Restrictions

[1] System configuration

1. Table of compatible indoor units
The table below summarizes the types of indoor units that are compatible with different types of outdoor units.
(1) Standard combinations
Outdoor units
(Heat source units)
(E)P200
(E)P250
(E)P300
(E)P350
(E)P400
(E)P450
(E)P500
(E)M200
(E)M250
(E)M300
(E)M350
(E)M400
(E)M450
(E)M500
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
3) Only either P**Y-W model indoor units (equipped with a flow control valve) or P**Y-WP/WL model indoor units (without a flow
control valve) can be connected to the HBC. (Combining different models of indoor units will cause a connection error.)
4) The following models of indoor units can be used as indoor units equipped with a flow control valve when used with the op-
tional valve kit (PAC-SK04VK-E).
<Applicable indoor units>
P**Y-WL**
* The optional valve kit (PAC-SK04VK-E) cannot be installed on P**Y-WP** models.
HWE1708A
HBC controller
Maximum total capacity
Sub-HBC
CMB-WM108V-AA,
CMB-WM1016V-AA
CMB-WM108V-AB,
CMB-WM1016V-AB
CMB-WM108V-BB,
CMB-WM1016V-BB
Maximum number
of connectable indoor
units
100 - 300
125 - 375
150 - 450
175 - 525
200 - 600
225 - 675
250 - 750
100 - 300
125 - 375
150 - 450
175 - 525
200 - 600
225 - 675
250 - 750
- 29 -
Types of connectable
of connectable in-
door units
30
W/WP/WL10- W/WP/
WL125 models
37
Indoor units for use with
HBC controller
45
50
50
50
50
30
37
45
50
50
50
50
indoor units
GB

Advertisement

Table of Contents
loading

Table of Contents