Environment; Ip Grade; Ambient Temperature; Atmospheric Conditions - Ingeteam Ingecon Sun Power Series Installation Manual

Table of Contents

Advertisement

Installation manual

2.1.1. Environment

CAUTION
Place the units in a place which is accessible for installation and maintenance work and which
permits use of the keyboard, the display and the reading of the front indicator LEDs.
CAUTION
The air vents and part of the cabinet close to them can reach 85 °C. Do not place any material nearby
which is sensitive high air temperatures.
CAUTION
Avoid corrosive environments that may affect the proper operation of the inverter.
CAUTION
Never place any object on top of the unit.

2.1.2. IP grade

Ingecon
Sun Power Max units have a IP20 level of protection against external agents.
®
IP20 means that the unit is fully protected against the ingress of dust and also against water streams from any direc-
tion as defined for this level of protection in standard IEC60529.
Ingecon
Sun Power should therefore be installed in an enclosed, covered location.
®
The environment in which they are assembled should always be dry and free of dust.
They are not suitable for outdoor installation.

2.1.3. Ambient temperature

These units are designed to operate in a temperature range from -20 °C to 65 °C. Nominal power may be input at up to
45 °C. Above this temperature the unit limits input power in order to cool the internal temperature of the electronics.

2.1.4. Atmospheric conditions

The ambient air must be clean and relative humidity must not exceed 50% at over 40 °C. Higher levels of relative
humidity, up to 95%, can be tolerated at below 30 °C.
It should be borne in mind that moderate condensation may occasionally occur as a consequence of temperature
variations. For this reason, apart from the unit's own protection, vigilance of these units is necessary once they have
been started up on sites where the conditions described above are not expected to be present.
In the event of condensation, never apply voltage to the unit.

2.1.5. Contamination class

The pollution class for which the units have been designed is grade 3.
Suitable measures should be taken to provide dust-free air of sufficient quality in the vicinity of the inverter.
2.1.6. Acoustic contaminación
When on, the inverter generates a buzzing sound.
Do not place it in an occupied room, or on light supports which might amplify this buzz. The mounting surface must
be firm and appropriate for the weight of the unit.
AAS2000IKI01
Ingeteam Power Technology, S.A.
11