9 RELAY COMMISSIONING
9.14.2.4 FUNCTION 32 2
ENERVISTA MII SETUP
FUNCTION 32 2
32_2 FUNCTION T2
Enable 32 2
32_2 Enable T2
Trip Enable 32 2
32_2 Trip T2
Power 32 2
32_2 Power Type T2
Type 32 2
32_2 Minimum/Maximum T2 Type 32 2
Direction 32 2
32_2 Forward/Reverse T2
Alarm Level 32 2
32_2 Alarm Level T2
Alarm Delay 32 2
32_2 Alarm Delay T2
Trip Level 32 2
32_2 Trip Level T2
Trip Delay 32 2
32_2 Trip Delay T2
Block 32 2
Block 32_2 From Online T2 Block 32 2
9.14.2.5 FUNCTION 32 3
ENERVISTA MII SETUP
FUNCTION 32 3
32_3 FUNCTION T2
Enable 32 3
32_3 Enable T2
Trip Enable 32 3
32_3 Trip T2
Power 32 3
32_3 Power Type T2
Type 32 3
32_3 Minimum/Maximum T2 Type 32 3
Direction 32 3
32_3 Forward/Reverse T2
Alarm Level 32 3
32_3 Alarm Level T2
Alarm Delay 32 3
32_3 Alarm Delay T2
Trip Level 32 3
32_3 Trip Level T2
Trip Delay 32 3
32_3 Trip Delay T2
Block 32 3
Block 32_3 From Online T2 Block 32 3
9.14.2.6 FUSE FAILURE (MIWII1000)
ENERVISTA MII SETUP
FUSE FAILURE
FUSE FAILURE T2
Enable Fuse
Fuse Failure Enable T2
GEK-113308
HMI
FUNCTION 32 2
Enable 32 2
Trip Enable 32 2
Power 32 2
Direction 32 2
Alarm Level 32 2
Alarm Delay 32 2
Trip Level 32 2
Trip Delay 32 2
HMI
FUNCTION 32 3
Enable 32 3
Trip Enable 32 3
Power 32 3
Direction 32 3
Alarm Level 32 3
Alarm Delay 32 3
Trip Level 32 3
Trip Delay 32 3
HMI
FUSE FAILURE
Enable Fuse
MIWII Directional Power Protection System
9.14 USER SETTINGS
SETTING
RANGE
YES/NO
YES/NO
ACTIVE /
REACTIVE /
APPARENT
MINIMUM /
MAXIMUM
FORWARD /
REVERSE
0.01 - 1.5
0.2 – 120 s
0.01 – 1.50
0.2 – 120 s
0 - 5000
SETTING
RANGE
YES/NO
YES/NO
ACTIVE /
REACTIVE /
APPARENT
MINIMUM /
MAXIMUM
FORWARD /
REVERSE
0.01 - 1.5
0.2 – 120 s
0.01 – 1.50
0.2 – 120 s
0 - 5000
SETTING
RANGE
YES/NO
STEP
NA
NA
NA
NA
0.01
0.01
0.1
0.01
0.1
1
STEP
NA
NA
NA
NA
0.01
0.01
0.1
0.01
0.1
1
STEP
NA
9
9-21