9.14 USER SETTINGS
9.14.1.2 FUNCTION 40 (MIWII1000)
FUNCTION 40
Enable 40
Volt Superv 40
Voltage Level 40
Trip Enable 40 1
Diam Circle 40 1
Offs Circle 40 1
Delay Circl 40 1
Trip Enable 40 2
Diam Circle 40 2
Offs Circle 40 2
Circle 2 timer
9.14.1.3 FUNCTION 32 1
FUNCTION 32 1
Enable 32 1
Trip Enable 32 1
Power 32 1
Type 32 1
Direction 32 1
Alarm Level 32 1
Alarm Delay 32 1
Trip Level 32 1
Trip Delay 32 1
Block 32 1
9
9-18
ENERVISTA MII
HMI
SETUP
40
FUNCTION 40
40 Enable
Enable 40
Enable Voltage
Volt Superv 40
Supervision
Voltage Level
Voltage Level 40
Enable Circle 1 Trip
Trip Enable 40 1
Circle 1 Diameter
Diam Circle 40 1
Circle 1 Offset
Offs Circle 40 1
Circle 1 Trip Delay
Delay Circl 40 1
Enable Circle 1 Trip
Trip Enable 40 2
Circle 2 Diameter
Diam Circle 40 2
Circle 2 Offset
Offs Circle 40 2
Circle 2 Trip Delay
TIME2 40
ENERVISTA MII SETUP
HMI
32_1 FUNCTION
FUNCTION 32 1
32_1 Enable
Enable 32 1
32_1 Trip
Trip Enable 32 1
32_1 Power Type
Power 32 1
32_1 Minimum/Maximum
Type 32 1
32_1 Forward/Reverse
Direction 32 1
32_1 Alarm Level
Alarm Level 32 1
32_1 Alarm Delay
Alarm Delay 32 1
32_1 Trip Level
Trip Level 32 1
32_1 Trip Delay
Trip Delay 32 1
Block 32_1 From Online
Block 32 1
MIWII Directional Power Protection System
9 RELAY COMMISSIONING
SETTING
RANGE
YES/NO
YES/NO
0.70 to 1.00 Vn
YES/NO
1 to 300 Ohm
1 to 180 Ohm
0.1 to 10 s
YES/NO
1 to 300 Ohm
1 to 280 Ohm
0.2 to 20 s
SETTING
RANGE
YES/NO
YES/NO
ACTIVE /
REACTIVE /
APPARENT
MINIMUM /
MAXIMUM
FORWARD /
REVERSE
0.01 - 1.50
0.2 – 120 s
0.01 - 1.50
0.2 – 120 s
0 - 5000
STEP
NA
NA
0.01
NA
0.1
0.1
0.1
NA
0.1
0.1
0.1
STEP
NA
NA
NA
NA
NA
0.01
0.1
0.01
0.1
1
GEK-113308