GE Multilin MIWII Instruction Manual page 152

Directional power protection system
Table of Contents

Advertisement

9.14 USER SETTINGS
9.14.1.2 FUNCTION 40 (MIWII1000)
FUNCTION 40
Enable 40
Volt Superv 40
Voltage Level 40
Trip Enable 40 1
Diam Circle 40 1
Offs Circle 40 1
Delay Circl 40 1
Trip Enable 40 2
Diam Circle 40 2
Offs Circle 40 2
Circle 2 timer
9.14.1.3 FUNCTION 32 1
FUNCTION 32 1
Enable 32 1
Trip Enable 32 1
Power 32 1
Type 32 1
Direction 32 1
Alarm Level 32 1
Alarm Delay 32 1
Trip Level 32 1
Trip Delay 32 1
Block 32 1
9
9-18
ENERVISTA MII
HMI
SETUP
40
FUNCTION 40
40 Enable
Enable 40
Enable Voltage
Volt Superv 40
Supervision
Voltage Level
Voltage Level 40
Enable Circle 1 Trip
Trip Enable 40 1
Circle 1 Diameter
Diam Circle 40 1
Circle 1 Offset
Offs Circle 40 1
Circle 1 Trip Delay
Delay Circl 40 1
Enable Circle 1 Trip
Trip Enable 40 2
Circle 2 Diameter
Diam Circle 40 2
Circle 2 Offset
Offs Circle 40 2
Circle 2 Trip Delay
TIME2 40
ENERVISTA MII SETUP
HMI
32_1 FUNCTION
FUNCTION 32 1
32_1 Enable
Enable 32 1
32_1 Trip
Trip Enable 32 1
32_1 Power Type
Power 32 1
32_1 Minimum/Maximum
Type 32 1
32_1 Forward/Reverse
Direction 32 1
32_1 Alarm Level
Alarm Level 32 1
32_1 Alarm Delay
Alarm Delay 32 1
32_1 Trip Level
Trip Level 32 1
32_1 Trip Delay
Trip Delay 32 1
Block 32_1 From Online
Block 32 1
MIWII Directional Power Protection System
9 RELAY COMMISSIONING
SETTING
RANGE
YES/NO
YES/NO
0.70 to 1.00 Vn
YES/NO
1 to 300 Ohm
1 to 180 Ohm
0.1 to 10 s
YES/NO
1 to 300 Ohm
1 to 280 Ohm
0.2 to 20 s
SETTING
RANGE
YES/NO
YES/NO
ACTIVE /
REACTIVE /
APPARENT
MINIMUM /
MAXIMUM
FORWARD /
REVERSE
0.01 - 1.50
0.2 – 120 s
0.01 - 1.50
0.2 – 120 s
0 - 5000
STEP
NA
NA
0.01
NA
0.1
0.1
0.1
NA
0.1
0.1
0.1
STEP
NA
NA
NA
NA
NA
0.01
0.1
0.01
0.1
1
GEK-113308