3.3.5 Fuses

Branch circuit protection:
In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines etc., must be short-circuited
and overcurrent protected according to national/international regulations.
Short-circuit protection:
The frequency converter must be protected against short-circuit to avoid electrical or fire hazard. Danfoss recommends using the fuses mentioned below
to protect service personnel and equipment in case of an internal failure in the drive. The frequency converter provides full short-circuit protection in case
of a short-circuit on the motor output.
Overcurrent protection:
Provide overload protection to avoid fire hazard due to overheating of the cables in the installation. The frequency converter is equipped with an internal
overcurrent protection that can be used for upstream overload protection (UL-applications excluded). See par. 4-18
circuit breakers can be used to provide the overcurrent protection in the installation. Overcurrent protection must always be carried out according to
national regulations.
Fuses must be designed for protection in a circuit capable of supplying a maximum of 100,000 A
Non UL compliance
If UL/cUL is not to be complied with, we recommend using the following fuses, which will ensure compliance with EN50178:
In case of malfunction, not following the recommendation may result in unnecessary damage to the frequency converter.
FC Type
K25-K75
1K1-2K2
3K0-3K7
5K5-7K5
11K
15K-18K5
22K
30K
37K
1) Max. fuses - refer to national/international regulations to select an appropriate fuse size.
98
99
W
1)
Motor voltage 0-100% of mains voltage.
PE
3 wires out of motor
W1
Delta-connected
PE
1)
V2
6 wires out of motor
W1
Star-connected U2, V2, W2
PE
1)
U2, V2 and W2 to be interconnected separately.
1)
Max. fuse size
10A
20A
32A
63A
80A
125A
160A
200A
250A
®
MG.33.AG.02 - VLT
is a registered Danfoss trademark
NB!
In motors without phase insulation paper or other in-
sulation reinforcement suitable for operation with volt-
age supply (such as a frequency converter), fit a Sine-
wave filter on the output of the frequency converter.
Current Limit
. Moreover, fuses or
(symmetrical), 500 V maximum.
rms
Min. rated Voltage
200-240 V
200-240 V
200-240 V
200-240 V
200-240 V
200-240 V
200-240 V
200-240 V
200-240 V
3 How to Install
3
Type
type gG
type gG
type gG
type gG
type gG
type gG
type aR
type aR
type aR
29