INVT Goodrive300-21 Series Operation Manual page 79

Dual-inverter integrated machine for air compressor
Hide thumbs Also See for Goodrive300-21 Series:
Table of Contents

Advertisement

Goodrive300-21 integrated machine for air compressor
P19.13
Status type
Low temperature
BIT14=1
protection pre-alarm
P19.14
Status type
Part 1 needs
BIT0=1
maintenance
Part 2 needs
BIT1=1
maintenance
Part 3 needs
BIT2=1
maintenance
Part 4 needs
BIT3=1
maintenance
Part 5 needs
BIT4=1
maintenance
Auxiliary pressure
BIT5=1
signal fault
Auxiliary
BIT6=1
temperature signal
The
detected by PT1 is less than
the low temperature protection
threshold set by P18.21.
Possible cause
The part 1 working hours
exceeds the set time in
P19.00.
The part 2 working hours
exceeds the set time in
P19.01.
The part 3 working hours
exceeds the set time in
P19.02.
The part 4 working hours
exceeds the set time in
P19.03.
The part 5 working hours
exceeds the set time in
P19.04.
The
detected by P2 is less than
1V.
PT100
disconnected.
fault
Possible cause
actual
temperature
actual
pressure
sensor
-
-
75
Solution
Temperature detection circuit is
abnormal.
Temperature detection sensor is
abnormal;
Temperature
detection
circuit is abnormal;
The actual temperature is too
low.
So
low
pre-alarm is released as normal
to prevent air compressor from
starting.
Solution
Stop and carry out maintenance.
Stop and carry out maintenance.
Stop and carry out maintenance.
Stop and carry out maintenance.
Stop and carry out maintenance.
Check if pressure detection sensor
is abnormal;
The input P2 signal wire of
pressure detection is dropped.
Detect if PT100 wiring is normal;
Temperature detection sensor is
is
abnormal;
Temperature detection circuit is
abnormal.
Troubleshooting
input
temperature