Analog Input As Setpoint Source - Siemens SINAMICS G110M Operating Instructions Manual

Distributed converter for simogear geared motors
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

Advanced commissioning
8.16 Setpoints
8.16.2

Analog input as setpoint source

Function description
Figure 8-38
In the quick commissioning, you define the preassignment for the converter interfaces.
Depending on what has been preassigned, after quick commissioning, the analog input can be
interconnected with the main setpoint.
Example
Setting with analog input 0 as setpoint source:
Parameter
p1070 = 755[0]
p1075 = 755[0]
Parameters
Number
r0755[0 ... 1]
p1070[C]
p1071[C]
r1073
p1075[C]
p1076[C]
r1077
260
Example: Analog input 0 as setpoint source
Description
Interconnects main setpoint with analog input 0
Interconnects supplementary setpoint with analog input 0
Name
CO: CU analog inputs, actual value in percent
CI: Main setpoint
CI: Main setpoint scaling
CO: Main setpoint active
CI: Supplementary setpoint
CI: Supplementary setpoint scaling
CO: Supplementary setpoint effective
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
Factory setting
- %
Dependent on the
converter
1
- rpm
0
1
- rpm