Installation
4.4 Connecting the converter to the fieldbus
Dual Slave
For automatic addressing, the address is specified by the AS-i master. If both slaves have address
0, the second slave is hidden and the control assigns a valid address for slave 1.
Slave 2 then becomes visible with address 0 and can be addressed.
Automatic addressing is not always possible for older AS-i masters. In this case, use the manual
addressing and set the address from an addressing device, via Startdrive or from an operator
panel on the converter.
Further information is contained in the AS-Interface system manual, Section "Setting the AS-i
address"
1171856)
Addressing via the addressing device (e.g. 3RK1904-2AB02)
Addressing via the addressing device is made offline.
Further information is contained in the AS-Interface system manual, Section "Setting the AS-i
address"
1171856)
Addressing via parameters
The address assignment is made with the p2012[0] and p2012[1] parameters.
If you assign the address via Startdrive, you must back up the settings so that they are not lost
if the power fails.
• Address range for Single Slave converter, profile 7.F.E
– p2012[1]: 0 ... 31, range for the A address, 0A ... 31A
• Address range for Dual Slave converter, profile 7.A.5 or 7.A.E
– p2012[0]: 0 ... 31, 33 ... 63 for slave 1:
– p2012[1]: 0 ... 31, 33 ... 63 for slave 2:
with
–
– 33 ... 63 range for B address, 1B ... 31B
96
AS-i System Interface Manual
AS-i System Interface Manual
0 ... 31 range for the A address, 0A ... 31A
(https://support.industry.siemens.com/cs/gb/en/view/
(https://support.industry.siemens.com/cs/gb/en/view/
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL