Application Example - Siemens SINAMICS G110M Operating Instructions Manual

Distributed converter for simogear geared motors
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

Appendix
A.2 Interconnecting signals in the converter
A.2.2

Application example

Shift the control logic into the converter
It is only permissible that a conveyor system starts when two signals are present simultaneously.
These could be the following signals, for example:
• The oil pump is running (the required pressure level is not reached, however, until after 5
seconds)
• The protective door is closed
To implement this task, you must insert free function blocks between digital input 0 and the
command to switch on the motor (ON/OFF1).
Figure A-4
The signal of digital input 0 (DI 0) is fed through a time block (PDE 0) and is interconnected with
the input of a logic block (AND 0). The signal of digital input 1 (DI 1) is interconnected to the
second input of the logic block. The logic block output issues the ON/OFF1 command to switch-
on the motor.
Setting the control logic
Parameter
p20161 = 5
p20162 = 430
p20032 = 5
p20033 = 440
p20159 = 5000.00
p20158 = 722.0
p20030[0] = 20160
p20030[1] = 722.1
p0840 = 20031
410
Signal interconnection for control logic
Description
The time block is enabled by assigning to runtime group 5 (time slice of
128 ms)
Run sequence of the time block within runtime group 5 (processing before
the AND logic block)
The AND logic block is enabled by assigning to runtime group 5 (time slice of
128 ms)
Run sequence of the AND logic block within runtime group 5 (processing
after the time block)
Setting the delay time [ms] of the time module: 5 seconds
Connect the status of DI 0 to the input of the time block
r0722.0 = Parameter that displays the status of digital input 0.
Interconnecting the time block to the 1st AND input
Interconnecting the status of DI 1 to the 2nd AND input
r0722.1 = Parameter that displays the status of digital input 1.
Interconnect the AND output to ON/OFF1
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents