If you change over from another telegram to telegram 20, then the assignment of the previous
1)
telegram is kept.
Status word 1 (ZSW1)
Bit Significance
0
1
2
3
4
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
Significance
Telegram 20
All other tele‐
grams
0 = Stop RFG
1 = Enable RFG
0 = Inhibit setpoint
1 = Enable setpoint
0 → 1 = Acknowledge faults
0 = No control via PLC
1 = Control via PLC
1 = Direction reversal
Not used
---
1 = MOP up
1)
---
1 = MOP down
1)
CDS bit 0
Reserved
Telegram 20
All other tele‐
grams
1 = Ready for switching on
1 = Ready
1 = Operation enabled
1 = Fault active
1 = OFF2 inactive
8.6 Drive control via PROFIBUS or PROFINET
Explanation
The output of the ramp-function generator
stops at the actual value.
The output of the ramp-function generator fol‐
lows the setpoint.
The converter brakes the motor with the ramp-
down time p1121 of the ramp-function gener‐
ator.
Motor accelerates to the setpoint with the ramp-
up time p1120.
Acknowledge fault. If the ON command is still
active, the converter switches to the "switching
on inhibited" state.
Converter ignores the process data from the
fieldbus.
Control via fieldbus, converter accepts the proc‐
ess data from the fieldbus.
Invert setpoint in the converter.
Increase the setpoint saved in the motorized po‐
tentiometer.
Reduce the setpoint saved in the motorized po‐
tentiometer.
Changes over between settings for different op‐
eration interfaces (command data sets).
Remarks
Power supply switched on; electronics initial‐
ized; pulses locked.
Motor is switched on (ON/OFF1 = 1), no fault is
active. With the command "Enable operation"
(STW1.3), the converter switches on the motor.
Motor follows setpoint. See control word 1,
bit 3.
The converter has a fault. Acknowledge fault
using STW1.7.
Coast down to standstill is not active.
Advanced commissioning
Signal inter‐
connection
in the con‐
verter
p1141[0] =
r2090.5
p1142[0] =
r2090.6
p2103[0] =
r2090.7
p0854[0] =
r2090.10
p1113[0] =
r2090.11
p1035[0] =
r2090.13
p1036[0] =
r2090.14
p0810 =
r2090.15
Signal inter‐
connection
in the con‐
verter
p2080[0] =
r0899.0
p2080[1] =
r0899.1
p2080[2] =
r0899.2
p2080[3] =
r2139.3
p2080[4] =
r0899.4
185