6. Check the acceleration behavior of the drive immediately after the motor has been switched
on:
– If the motor holding brake opens too late, the converter will accelerate the motor
– If the motor waits too long before accelerating after the motor holding brake has opened,
7. If the load sags after switching on the motor, then you must increase the motor torque when
opening the motor holding brake. Depending on the control mode, you must set different
parameters:
– U/f control (p1300 = 0 to 3):
– Vector control (p1300 ≥ 20):
8. Switch off the motor.
9. Check the behavior of the drive immediately after the motor has been switched off:
– If the motor holding brake closes too late, the load briefly sags before the motor holding
– If the motor waits too long before switching off after the motor holding brake has closed,
The "Motor holding brake" function has been commissioned.
Parameter
Table 8-40
Parameter
r0052.0...15
p1215
p1216
p1217
Table 8-41
Parameter
p0346[M]
p0855[C]
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
suddenly against the closed motor holding brake.
Set p1216 larger.
reduce p1216.
For applications involving a pulling load, e.g. lifting gear/crane, if p1216 is too long, then
the load can briefly sag/sink after the motor holding brake is opened. If you reduce p1216,
then the amount that the load sags/sinks is reduced.
Increase p1310 in small steps.
Increase p1351 in small steps.
Increase p1475 in small steps.
brake closes.
Set a larger value for p1217.
reduce p1217.
Setting the control logic of the motor holding brake
Description
CO/BO: Status word 1
Motor holding brake configuration
Motor holding brake opening time
Motor holding brake closing time
Advanced settings
Description
Motor excitation build-up time
BI: Unconditionally open holding brake
Advanced commissioning
8.12 Motor holding brake
Factory setting
-
0
100 ms
100 ms
Factory setting
0 s
0
233