Requirement
The following preconditions apply:
• The converter power supply has been switched on.
• The PC and converter are connected with one another via a USB cable or via the fieldbus.
• A memory card is inserted in the converter.
Function description
Procedure
1. Go online.
2. Select "Online & diagnostics".
3. Select "Back up/reset".
4. Back up the settings to the EEPROM of the converter.
5. Set the number of your data backup. You can back up 99 different settings on the memory
card.
6. Start data transfer
7. Wait until Startdrive signals that data backup has been completed.
You have backed up the converter settings to a memory card.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
Uploading the converter settings
6.2 Uploading to the memory card
141