7. Connect the motor temperature sensor
8. Connecting the mains earth cable (HANQ variant)
9. Connecting the mains cables (HANQ variant)
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
1. Connect the motor temperature sensor cables to the tem‐
perature sensor terminal block.
2. Ensure that the cable is clear of any obstructions and does not
restrict access to other cables and connectors within the Ter‐
minal Housing.
Connect the motor temperature sensor (second part)
1. Connect the second part of the motor temperature sensor
cable to the temperature sensor terminal block.
2. The connector on the second part of the motor temperature
sensor is plugged into the Communications and Power Inter‐
face (CPI).
Notes:
• The motor temperature sensor terminal block has a diameter
of 2.79 mm.
• The final connection of the temperature sensor cannot be
completed until the CPI has been fitted. This will be done after
the CPI is fitted, as shown later in this procedure.
1. Connect the HANQ earth connection to the earthing post of
the Terminal Housing.
2. Tighten the earthing post screw to 1.5 Nm.
Note:
If the SINAMICS G110M is ordered as a complete system, then all
mechanical and electrical installation is completed in the factory
prior to delivery.
1. Ensure that the cable clamp has been removed.
2. Connect the HANQ L1, L2 and L3 connections to the L1, L2
and L3 connections on the mains connector.
3. When the connections are completed, replace the cable
clamp over the cables (ensuring that the cable clamp is the
correct way round).
Note:
Tightening torque of the mains terminals are a maximum of 0.8
Nm.