3.36. Key functions

The Advanced Power Controller key allows the status of the
device to be changed.
A pressing and holding the key changes the status; the
length of time key is pressed determines the new status.
Release the key before switching to another status.
The arrival status is determined by the departure status.
When the key is pressed, the RN and BUT LEDs light up
steadily and then go out after 2 or 3 seconds to indicate the
change of status.
Key functions
Ready for PF alarm reset with
memory
Key
pressed
> 1 sec.
LED RN steadily on
LED BUT
2 flashes per
second.
Reset PF alarms with memory
LED RN
flashing rapidly
LED BUT
flashing rapidly
LED colours
LED RN
Green
LED ER
Red
LED 01
Yellow
LED BUT
Yellow
LED RN flashing
LED BUT off
Ready for HB alarm calibration
Key
pressed
> 1 sec.
LED RN steadily on
LED BUT 1 flash per second.
Key pressed > 3 sec.
LED RN
LED BUT
81901 "MSW_GPC-40/600A"_03-2021_ENG_page 134
Example of key use
To activate the HB alarm calibration, start from normal op-
eration (RN LED flashing, BUT LED off):
1.
press and hold the key for at least 3 seconds, the LEDs
will light up steadily;
2.
release the key;
3.
wait for the LEDs to go out;
4.
press the key again for at least 3 seconds;
5.
wait for the LEDs to go out;
6.
the HB alarm calibration procedure starts (LEDs flash
rapidly);
7.
When the LEDs resume normal operation, the calibra-
tion procedure is complete.
The following diagram shows how to use the key.
Each box represents a status, which is identified in the grey
area.
Normal operation
Key pressed > 3 sec.
Key pressed > 3 sec.
HB alarm calibration
flashing rapidly
flashing rapidly
Alarms
FUSE_OPEN
SHORT_CIRCUIT_CURRENT
Single-phase configuration
LED RN flashing
LED ER flashing
LED BUT off
Three-phase configuration
All LEDs flashing rapidly
except:
LED BUT
FUSE_OPEN
alarm
or
LED 01 SHORT_
CIRCUIT_
CURRENT alarm
Key pressed > 2 sec.
Reset
FUSE_OPEN
SHORT_CIRCUIT_CURRENT
alarms
LED RN
off
LED BUT
off

Advertisement