Automatic - Manual Control; Manual Power; Automatic - Manual Selection - gefran GPC Configuration And Programming Manual

Advanced power controller
Table of Contents

Advertisement

3.22. Automatic - manual control

The digital input function can be used to put the Advanced
Power Controller in MAN (manual) status and set the control
output to a constant value, which can be changed via serial
communication.
When returning to AUTO (automatic) status, the transition
from manual mode will be based upon the reference power
(SPU_x) and the control output gradient (G.out).
3.22.1.

Manual power

Address
Format
Single-
Multi-
node
node
1276
2300
252
16 bit
4348
The parameter sets the percentage of manual power.
min...max: -100.0...100.0
3.22.2.

Automatic - manual selection

Address
Format
Single-
Multi-
node
node
1025
2049
1
bit
4097
The bit sets the automatic/manual operation of the Advanced Power Controller.
OFF
Options:
= Automatic
ON
= Manual
GPC-OP
Acronym
menu
07.02.01
M
MAN-
07.03.01
UAL_
E1
POWER
01.04.01
E2
GPC-OP
Acronym
menu
12.01.01
M
BIT_
12.02.01
AUTO_
E1
MAN
12.03.01
E2
81901A "MSW_GPC-40/600A"_03-2021_ENG_page 101
In addition to the parameters shown below, the following
parameters should also be considered for automatic - man-
ual control:
digital input function dIG.1 / dIG.2 / dIG.3 / dIG.4 (see
paragraph "3.12.4. Digital input function");
value of the control output Ou.P (see paragraph
"3.21.2. Output power value").
GF_eXpress menu
Description
MainMenu → M → Controls →
MANUAL_POWER_1
MainMenu → E1 → Controls →
MANUAL_POWER_2
MainMenu → E2 → Controls →
MANUAL_POWER_3
GF_eXpress menu
Description
MainMenu → M → Expert →
Bit → BIT_AUTO_MAN_1
MainMenu → E1 → Expert →
Bit → BIT_AUTO_MAN_2
MainMenu → E2 → Expert →
Bit → BIT_AUTO_MAN_3
Float
R/W
%
(####.#)
Unsigned
R/W
Short
0.0
OFF

Advertisement

Table of Contents
loading

Table of Contents