Address
GPC-OP
Format
Single-
Multi-
node
node
The parameter sets the reference variable for the generic alarms AL1...AL8 of modules GPC-M, GPC-E1 and GPC-E2. The alarm and
module concerned depend on the address used. The range of valid values and the position of the decimal point for alarm threshold and
hysteresis can vary depending on the reference variable chosen for the alarm.
Options:
Index
9
In.A1: Analog input 1
In.Pwm1: input PWM 1
10
11
In.A2: Analog input 2
12
In.A3: Analog input 3
13
In.Pwm2: input PWM 2
14
In.Pwm3: input PWM 3
15
I.tA_x: instantaneous load current of module x *
16
I.tV_x: instantaneous line voltage of module x *
17
I.on_x: Load current of module x at activated output *
18
I.VF_x: Filtered line voltage of module x *
19
Ld.I_x: load impedance of module x *
20
In.Ntc.SSR_x: SSR heat sink temperature of module x *
21
In.Ntc.LINE_x: LINE terminal temperature of module x *
22
In.Ntc.LOAD_x: LOAD terminal temperature of module x *
*) x = 1 identifies GPC-M, x = 2 identifies GPC-E1; x = 3 identifies GPC-E2
Acronym
menu
Variable for comparison
81901A "MSW_GPC-40/600A"_03-2021_ENG_page 45
GF_eXpress menu
Description
Reference
threshold
AL.y
(with y = 1...8)
Alarm threshold
Decimal point
range
position
LS.A1...HS.A1
###.#
0.0...100.0
###.#
LS.A2...HS.A2
###.#
LS.A3...HS.A3
###.#
0.0...100.0
###.#
0.0...100.0
###.#
L.tA_x...H.tA_x *
###.#
L.tV_x...H.tV_x *
###.#
L.tA_x...H.tA_x *
###.#
L.tV_x...H.tV_x *
###.#
0.00...655.35
####.##
10.0...120.0
###.#
10.0...120.0
###.#
10.0...120.0
###.#

Advertisement