Hb Alarm Threshold As Function Of Power On Load; Hb (Or Ta1-Ta2-Ta3) Or Power Fault Alarm Status - gefran GPC Configuration And Programming Manual

Advanced power controller
Table of Contents

Advertisement

Address
Format
Single-
Multi-
node
node
The parameter sets the HB calibration when using IR lamps. The following table shows the correspondence between acronym and per-
centage of conduction voltage.
min...max:
0.0...999.9
For details of HB calibration with IR lamps see paragraph "4.4.3. HB alarm threshold teach-in function".
3.14.12.

HB alarm threshold as function of power on load

Address
Format
Single-
Multi-
node
node
1768
2792
744
16 bit
4840
The parameter shows the HB alarm threshold as a function of the power on the load.
min...max:
0.0...3275.0
3.14.13.

HB (OR TA1-TA2-TA3) OR POWER FAULT alarm status

Address
Format
Single-
Multi-
node
node
1050
2074
26
bit
4122
The parameter shows the HB (OR TA1-TA2-TA3) OR POWER_FAULT alarm status.
Options:
OFF
= Alarm off
ON
= Alarm on
GPC-OP
Acronym
menu
Acronym
Ir.tV.0
Ir.tV.1
Ir.tV.2
Ir.tV.3
Ir.tV.4
Ir.tV.5
Ir.tV.6
Ir.tV.7
Ir.tV.8
Ir.tV.9
GPC-OP
Acronym
menu
M
Hb.tr
E1
E2
GPC-OP
Acronym
menu
M
BIT_
STATUS_
E1
HB_OR_
PF
E2
81901A "MSW_GPC-40/600A"_03-2021_ENG_page 69
GF_eXpress menu
Description
Voltage
100 % conduction
50 % conduction
30 % conduction
20 % conduction
15 % conduction
10 % conduction
5 % conduction
3 % conduction
2 % conduction
1 % conduction
GF_eXpress menu
Description
MainMenu → M → Alarms →
HB alarm → Hb.tr_1
MainMenu → E1 → Alarms →
HB alarm → Hb.tr_2
MainMenu → E2 → Alarms →
HB alarm → Hb.tr_3
GF_eXpress menu
Description
MainMenu → M → Expert → Bit →
BIT_STATUS_HB_OR_PF_1
MainMenu → M → Expert → Bit →
BIT_STATUS_HB_OR_PF_2
MainMenu → M → Expert → Bit →
BIT_STATUS_HB_OR_PF_3
Float
R
A
(####.#)
R