HEATING OUTPUT (Fast cycle)

For output rL.1 (corresponding to physical output Out 1), you can set a fast cycle time (0.1 ... 20.0 sec.) by setting
parameter rL.1 to 64 (Ou.P function).
152*
R/W
[t.1

OPERATING HOUR METER

The device shows in OH. c (Operating Hours Counter) the number of operating hours (line voltage present and non-
zero power); updating in non-volatile memory occurs every two hours and the disarming of the line voltage.
396*
R
0K.c
56

OTHER FUNCTIONS

OUT1 cycle time
hours of operation
1...200 sec.
(*)
(0.1...20.0 sec.)
(*)Set to 0 for BF/HSC functions
See Power management
Data format: Dword (32 bit)
80997D_MSW_GFW_400-600_04-2021_ENG
DIP 5 = OFF
(Resistive load)
0
0
0
Zone 1
Zone 2
Zone 3
DIP 5 = ON
(Inductive load)
4
4
4
Zone 1
Zone 2
Zone 3