gefran GFX4-IR Configuration And Programming Manual

4-zone modular power controller for ir lamps and inductive loads

Advertisement

LIST OF ATTACHMENTS

This document supplements the following manuals:
- Instructions and warnings for GFXTERMO4
- Instructions and warnings for GFX4
80415F_MSW_GFX4-IR_05-2019_ENG
GFX4-IR
4-ZONE MODULAR POWER CONTROLLER FOR IR LAMPS AND INDUCTIVE
LOADS
CONFIGURATION AND
PROGRAMMING MANUAL
Software version: 1.4x
code: 80415F - 05/2019 - ENGLISH
ATTENTION!
This manual is an integral part of the product,
and must always be available to operators.
This manual must always accompany the pro-
duct, including if it is transferred to another user.
Installation and/or maintenance workers MUST
read this manual and scrupulously follow all of the in-
structions in it and in its attachments. GEFRAN will not
be liable for damage to persons and/or property, or to
the product itself, if the following terms and conditions
are disregarded.
The Customer is obligated to respect trade
secrets. Therefore, this manual and its attachments
may not be tampered with, changed, reproduced,
or transferred to third parties without GEFRAN's
authorization.
1

Advertisement

Table of Contents
loading

Summary of Contents for gefran GFX4-IR

  • Page 1: List Of Attachments

    Installation and/or maintenance workers MUST read this manual and scrupulously follow all of the in- structions in it and in its attachments. GEFRAN will not be liable for damage to persons and/or property, or to the product itself, if the following terms and conditions are disregarded.
  • Page 2 80415F_MSW_GFX4-IR_05-2019_ENG...
  • Page 3: Table Of Contents

    TABLE OF CONTENTS AND SUMMARIES OUTPUTS .................39 LIST OF ATTACHMENTS ..........1 ALLOCATION OF REFERENCE SIGNALS .....39 TABLE OF CONTENTS AND SUMMARIES .....3 ALLOCATION OF PHYSICAL OUTPUTS ....40 INTRODUCTION ..............4 SETTINGS .................43 FIELD OF USE ..............4 SETTING THE SETPOINT ...........43 CHARACTERISTICS OF PERSONNEL ......4 SETPOINT CONTROL ..........44 STRUCTURE OF THIS MANUAL ........5 CONTROLS ..............46...
  • Page 4: Introduction

    Since it is impossible to foresee all of the installations and environments in which the instrument may be applied, adequate technical preparation and complete knowledge of the instrument’s potentials are necessary. GEFRAN declines all liability if rules for correct installation, configuration, and/or programming are disregarded, as well as all liability for systems upline and/or downline of the instrument.
  • Page 5: Structure Of This Manual

    This manual was originally written in ITALIAN. Therefore, in case of inconsistencies or doubts, request the original manual or explanations from GEFRAN. The instructions in this manual do not replace the safety instructions and the technical data for installation, configuration and programming applied directly to the product or the rules of common sense and safety regulations in effect in the country of installation.
  • Page 6: Instrument Architecture

    INSTRUMENT ARCHITECTURE The modular power controller’s flexibility permits replacement of previous-version instruments without changing the control software in use. Based on the chosen work mode (see MODBUS SERIAL COMMUNICATION), you can use the instrument in 2 different modes: - GFX compatible mode: as if there were 4 separate instruments (recommended for retrofitting projects and/or replacement of damaged instruments);...
  • Page 7: Serial Communication (Modbus)

    SERIAL COMMUNICATION (MODBUS) There are two Modbus addressing modes for variables and configuration parameters: - GFX compatible - GFX4 The modes are selected with dip-switch-7. All the parameters of formulation are saved in internal storage EEPROM (not flown them), of which a maximum of 100.000 cycles of cancellation is guaranteed/ writing.
  • Page 8: Connection

    There is a single value (Cod) set on the rotary switches; i.e., one for each GFX4-IR instrument. To access the data in each zone, simply add an offset to the address (+1024 for Zone 1, +2048 for Zone 2, +4096 for Zone 3, +8192 for Zone 4).
  • Page 9 - parity Serial 2 = none You can install a maximum of 99 GFX4-IR modules in a serial network, with node address selectable from “01” to “99” in stan- dard mode, or create a mixed GFX4-IR/ GFX4 / Geflex network in Geflex compatible mode in which each GFX4-IR or GFX4 identifies 4 zones with sequential node address starting from the code set on the rotary switches.
  • Page 10: Inputs

    INPUTS MAIN INPUT The modular power controller has 4 main inputs to control 4 temperature zones, to which you can connect temperature sensors (thermocouples and RTD), linear sensors or custom sensors to acquire process variable (PV) values. To configure, you always have to define the type of probe or sensor (tYP), the maximum and minimum scale limit (Hi. S –...
  • Page 11 Probes and sensors tYP. Table of probes and sensors Probe type, signal, enable, custom linearization and main input scale TC SENSOR Type Type of probe Scale Without dec. point With dec. point TC J °C 0/1000 0.0/999.9 TC J °F 32/1832 32.0/999.9 TC K...
  • Page 12 Read state In. 1 Main input value Read of engineering value of P.V. process variable (PV) Self-diagnostic error code Error code table of main input No Error For custom linearization (tYP = 28 or 29): Lo (process variable value is < Lo.S) - LO is signaled with input values below Lo.S or at minimum Hi (process variable value is >...
  • Page 13 The engineering values calculated in this way by the user can be set by means of the following parameters. Engineering value attributed to Point 0 S. 0 0 (- 1999 ... 9999) (minimum value of input scale) Engineering value attributed to S.
  • Page 14: Current Value On Load

    CURRENT VALUE IN LOAD The RMS current value is read in variable Ld.A of each zone. If zone 1 has a 3-phase load, variable Ld.At contains the average value of the three RMS currents. The Ld.A of the first three zones contain the RMS current value on lines L1, L2 and L3, respectively..
  • Page 15 Setting the offset Offset correction CT input -99.9 ...99.9 o. t A1 (phase 1) scale points -99.9 ...99.9 Offset correction CT input o. t A2 With 3-phase load (phase 2) scale points Offset correction CT input -99.9 ...99.9 o. t A3 With 3-phase load (phase 3) scale points...
  • Page 16 FUNCTIONAL DIAGRAM Monophase load Low pass Internal variable I.tA1 Offset scale CT1 auxi- See generic alarms and filter limits liary input HB alarms (Ft.tA) (H.tA1, o.tA1) Internal variable I.1On FUNCTIONAL DIAGRAM Threephase load Low pass Offset scale Variable L.dA zone 1 filter limits auxiliary input...
  • Page 17: Voltage Value On Load

    VOLTAGE VALUE ON LOAD RMS voltage is read in variable Ld.V of each zone. If zone 1 has a 3-phase load, variable Ld.V.t in the first zone contains the average RMS value of voltages of the three lines L1, L2 and L3. Voltage on the load is acquired with sampling on each cycle, 20ms at 50Hz (16.6ms at 60Hz).
  • Page 18 Setting the offset Offset correction for TV input -99.9 ...99.9 o. t U1 (phase 1) Scale points Offset correction for TV input -99.9 ...99.9 o. t U2 With 3-phase load (phase 2) Scale points Offset correction for TV input -99.9 ...99.9 o.
  • Page 19 ADVANCED SETTINGS Input filter Digital filter for auxiliary TV input (phase FT. T U 0.0 ... 20.0 sec. 1, 2 and 3) Sets a low pass filter on the auxiliary TV input, running the average of values read in the specified time interval.
  • Page 20: Power On Load

    POWER ON LOAD Power on the load in each zone is read in variable Ld.P Impedance in each zone is read in variable Ld.I. If zone 1 has a 3-phase load, variable Ld.P.t shows power and Ld.I.t total impedance. Note that for loads such as IR lamps, impedance can vary greatly based on the power transferred to the load. Ld.
  • Page 21: Auxiliary Analog Input (Lin/Tc)

    AUXILIARY ANALOG INPUT (LIN/TC) The GFX4-IR has 4 inputs defined as auxiliary (IN5 for zone 1, IN6 for zone 2, IN7 for zone 3, IN8 for zone 4) to which TC or linear temperature sensors can be connected. The presence of these inputs is optional and, for model GFX4-IR-x-x-4-x-x is defined by the order code.
  • Page 22 Read state In. 2 Value of auxiliary input Error code for self-diagnosis Er. 2 Error code table of auxiliary input No error Lo (value of process variable is < Lo.S) Hi (value of process variable is > Hi.S) ERR [third wire interrupted for PT100 or input values below minimum limits (ex.: for TC with connection error)] SBR (probe interrupted or input values beyond maximum limits) ADVANCED SETTINGS...
  • Page 23: Digital Inputs

    DIGITAL INPUTS There are always two inputs. Each input can perform various functions based on the setting of the following parameters: diG. Digital input function Digital input functions table Activation No functions (input off) On leading edge MAN/AUTO controller diG. 2 Digital input 2 function On leading edge LOC / REM...
  • Page 24: Using A Function Associated With Digital Input And Via Serial

    USING A FUNCTION ASSOCIATED WITH DIGITAL INPUT AND VIA SERIAL At power-on or on the leading edge of digital input 1 or 2, all zones assume the state set by the digital input. For each zone, this state can be changed by writing via serial. The setting via serial is saved in eeprom (STATUS_W_EEP, address 698).
  • Page 25: Using A Function Of Digital Input 1 To Enable At Software On

    USING A FUNCTION OF DIGITAL INPUT 1 TO ENABLE AT SOFTWARE ON Software ON can be configured either by enabling a digital input or by writing via serial. Enabling by digital input 1 1 (diG) is common to all zones, whereas enabling via serial is specific for each individual zone. The ON/OFF setting via serial is saved in eeprom (STATUS_W_EEP, address 698 bit 3) for resetting of the condition at the next hardware power-on;...
  • Page 26: Alarms

    ALARMS GENERIC ALARMS AL1, AL2, AL3 and AL4 Four generic alarms are always available and can perform various functions. Typically, alarm AL.1 is defined as minimum and AL.2 as maximum. These alarms are set as follows: - select the reference variable to be used to monitor the value (parameters A1.r, A2.r, A3.r and A4.r): the origin of the variable can be chosen from the process variable PV (generally linked to the main input), the ammeter input, the voltmeter input, the auxiliary analog input, or the active setpoint.
  • Page 27 Reference variables a1. r Select reference variable alarm 1 Table of alarm reference setpoints Variable to be compared Reference setpoint A2. r Select reference variable alarm 2 PV (process variable) in.tA1 (In.tA1 OR In.tA2 OR In.tA3 WITH 3-PHASE LOAD) A3. r Select reference variable alarm 3 In.tV1 (In.tV1 OR In.tV2 OR In.tV3...
  • Page 28 Alarm type a1. t Alarm type 1 Table of alarm behaviour Direct (high limit) Absolute Normal A2. t Alarm type 2 Inverse (low limit) Relative Symmetrical to activfe setpoint (window) direct absolute normal inverse absolute normal A3. t Alarm type 3 direct relative normal...
  • Page 29 Enable alarms AL. n Select number of enabled alarms Table of enabled alarms Alarm 1 Alarm 2 Alarm 3 Alarm 4 disabled disabled disabled disabled enabled disabled disabled disabled disabled enabled disabled disabled enabled enabled disabled disabled disabled disabled enabled disabled enabled disabled...
  • Page 30 FUNCTIONAL DIAGRAM Type of alarm Alarm setpoint State of alarm AL1 and hysteresis (A1.t, HY.1) Type of alarm Alarm setpoint State of alarm AL2 and hysteresis (A2.t, HY.2) See outputs Type of alarm Alarm setpoint State of alarm AL3 and hysteresis (A3.t, HY.3) Alarm setpoint Type of alarm...
  • Page 31: Lba Alarm (Loop Break Alarm)

    LBA ALARM (Loop Break Alarm) This alarm identifies incorrect functioning of the control loop due to a possible load break or to a short circuited or reversed probe. With the alarm enabled (parameter AL.n), the instrument checks that in condition of maximum power delivered for a settable time (Lb.t) greater than zero, the value of the process variable increases in heating or decreases in cooling: if this does not happen, the LBA alarm trips.
  • Page 32: Hb Alarm (Heater Break Alarm)

    HB ALARM (Heater Break Alarm) This type of alarm identifies load break or interruption by reading the current delivered by means of a current tran- sformer. The following three fault situations may occur: - delivered current is lower than theoretical current: this is the most common situation, and indicates that a load ele- ment is breaking.
  • Page 33 Enable alarm AL. n Select number of enabled alarms See: Table of enable alarms Xb. f HB alarm functions Table of HB alarm functions Relay, logic output: alarm active at a load current value below Default: set point for control output ON time. SINGLE-PHASE LOAD: each A.HbX refers to its respective phase.
  • Page 34 Read state HB alarm setpoint as function xb. t r of power on load HB ALARM STATE OR OFF = Alarm off POWER_FAULT ON = Alarm on State of HB alarm phase 1 State of HB alarm with 3-phase loads phase 2 State of HB alarm with 3-phase loads...
  • Page 35 FUNCTIONAL DIAGRAM HB Alarm Alarm setpoint Hb.tr zone 1 State of alarm HB phase 1 I.1on Function of Alarm setpoint HB alarm State of alarm HB phase 2 (*) Hb.tr zone 2 (*) and time for activation See outputs I.2on of HB alarm (Hb.F, Hb.t) State of alarm HB phase 3 (*)
  • Page 36: Sbr - Err Alarms

    ALARM SBR - ERR (probe in short or connection error) This alarm is always ON and cannot be deactivated. It controls correct functioning of the probe connected to the main input. In case of broken probe: - the state of alarms AL1, AL2, AL3 and AL4 is set based on the value of parameter rEL; - control power control is set to the value of parameter FAP.
  • Page 37: Power Fault Alarms

    Power Fault ALARMS (SSR_SHORT , NO_VOLTAGE, SSR_OPEN and NO_CURRENT) hd. 2 Enable POWER_FAULT alarms Table of Power Fault alarms SSR_ SHORT NO_ VOLTAGE NO_CURRENT + 32 alarms with memory Refresh rate SSR SHORT dg. t 1...999 sec The alarm activates after 3 seconds. Time filter for NO_VOLTAGE, SSR_OPEN and NO_CURRENT alarms dg.
  • Page 38: Overheat Alarm

    Overheat alarm The controller has a temperature sensor for the internal heatsink. The temperature value of the heatsink is in variable INPTC; the over_heat alarm trips when the temperature exceeds 85°C. This condition may be caused by obstructed air vents or by a blocked cooling fan. The over-heat alarm is cancelled when the heat sink temperature falls below the value of 75°C.
  • Page 39: Outputs

    OUTPUTS The modular power controller has high flexibility in the assignment of functions to the physical outputs. As a result, the instrument can be used in sophisticated applications. A function is assigned to each physical output in two steps: first assign the function to one of internal reference signals rL.1 ..
  • Page 40: Allocation Of Physical Outputs

    2 AL1 - alarm 1 3 AL2 - alarm 2 rL. 3 Allocation of reference signal 4 AL3 - alarm 3 5 AL.HB or POWER_FAULT with HB alarm (TA1 OR TA2 OR TA3) 6 LBA - LBA alarm rL. 4 Allocation of reference signal 7 IN1 - repetition of logic input DIG1 8 AL4 - alarm 4...
  • Page 41 ALLOCATION OF PHYSICAL OUTPUTS ovt. 1 Allocation of physical output OUT 1 Table of output allocations ovt. 2 Allocation of physical output OUT 2 Output disabled Output rL.1 zone 1 Output rL.1 zone 2 ovt. 3 Allocation of physical output OUT 3 Output rL.1 zone 3 Output rL.1 zone 4 Output rL.2 zone 1...
  • Page 42 FUNCTIONAL DIAGRAM Ou.P (Heat) rL.1 - Zone1 Ou.P (Cool) State of AL1 rL.2 - Zone1 State of AL2 Allocation State of AL3 of reference State of AL4 signal (rL.1, rL.2, rL.3 or rL.5 - Zone1 State of Hb.1 rL.3, rL.4, rL.5, rL.6) State of Hb.2 * State of Hb.3 *...
  • Page 43: Settings

    SETTINGS The controller has the following setpoint controls. SETTING THE SETPOINT The active (control) setpoint (SPA) can be set by means of the local setpoint (_SP) or the remote setpoint (SP.rS). A remote setpoint can assume the value of an auxiliary input or one set via serial line (SP.r). The remote setpoint can be defined in absolute value or relative to the local setpoint;...
  • Page 44: Setpoint Control

    SETPOINT CONTROL Set gradient The “Set gradient” function sets a gradual variation of the setpoint, with programmed speed, between two defined values. If this function is active ( other than 0), at switch- g. s p Absolute alarm Setpoint profile on and at auto/man switching the initial setpoint is assumed Referred to current setpoint...
  • Page 45 diG. Digital input function See: Table of digital input functions diG. 2 Digital input function 2 See: Table of digital input functions SELECT OFF = Select SP1 SP1 / SP2 ON = Select SP2 Instrument state (STATUS_W) Table of instrument settings Select SP1/SP2 Start/Stop Selftuning Select ON/OFF...
  • Page 46: Controls

    If the Integral Time value is too long (weak Integral Action), there may be persistent deviation between the controlled variable and the setpoint. For more information on control actions, contact GEFRAN. 80415F_MSW_GFX4-IR_05-2019_ENG...
  • Page 47 Heat/cool control with separate or superimposed band Output with separate band Output with superimposed band Control output with only proportional action in case of proportional Control output with only proportional action in case of proportional heating band separate from cooling band. heating band superimposed on cooling band.
  • Page 48 Proportional band for heating or hyste- h. p b 0.0 ...999.9% f.s. resis ON/OFF 148 - 149 4.00 h. 1 t Integral heating time 0.00 ...99.99 min 1.00 h. d t Derivative heating time 0.00 ...99.99 min Proportional band for cooling or hyste- c.
  • Page 49 FUNCTIONAL DIAGRAM (h.Pb, Active setpoint h.it, h.dt, Output (SPA) Power of c.SP, c.Pb, PID_POWER power reference h.b,rSt,A.rS) limits (SPU) In.1 - zone1 Enable PV In.1 - zone2 for zone (SPU) In.1 - zone3 In.1 - zone4 PID_POWER zone 1 PID_POWER zone 2 Power limit for Fault Action (FA.P) PID_POWER zone 3...
  • Page 50: Automatic / Manual Control

    AUTOMATIC / MANUAL CONTROL By means of the digital input function you can set the controller in MAN (manual) and set the control output to a constant value changeable by means of communication. When returning to AUTO (automatic), if the variable is within the proportional band, switching is bumpless. MANUAL_POWER -100.0...100.0% Value of control outputs...
  • Page 51: Manual Tuning

    MANUAL TUNING A) Enter the setpoint at its working value. B) Set the proportional band at 0.1% (with on-off type set- ting). C) Switch to automatic and observe the behavior of the varia- Process ble. It will be similar to that in the figure: variable D) The PID parameters are calculated as follows: Proportional band...
  • Page 52 Enable selftuning, s. t v Selftuning, autotuning, softstart table autotuning, softstart Autotuning Selftuning Softstart continuous Autotuning One-shot WAIT WAIT WAIT (*) +16 with automatic switching in GO if PV-SP > 0.5% f.s. +32 with automatic switching in GO if PV-SP > 1% f.s. +64 with automatic switching in GO if PV-SP >...
  • Page 53: Selftuning

    SELFTUNING This function is valid for single-action (either heat or cool) systems and for double-action (heat/cool) systems. Selftuning is activated to calculate the best control parameters when starting the process. The variable (example: temperature) must be the one assumed at zero power (room temperature). The controller supplies the maximum power set until reaching an intermediate point between starting value and the setpoint, then resets power.
  • Page 54: Softstart

    Read state OFF = Selftuning in Stop SELFTUNING STATE ON = Selftuning in Start STATE OF DIGITAL OFF = Digital input 1 off See: Table of digital input functions INPUT 1 ON = Digital input 1 on STATE OF DIGITAL OFF = Digital input 2 off INPUT 2 ON = Digital input 2 on...
  • Page 55: Software Shutdown

    SOFTWARE SHUTDOWN Running the software shutdown procedure causes the following: 1) Reset of Autotuning, Selftuning and Softstart. 2) Digital input (if present) enabled only if assigned to SW shutdown function. 3) In case of switch-on after SW shutdown, any ramp for the set (set gradient) starts from the PV. 4) Outputs OFF: except for rL.4 and rL.6 which are forced ON.
  • Page 56: Hot Runners Control

    HOT RUNNERS CONTROL With the following parameters, you can perform a specific control for the hot runners (hot.runners). The main functions are: FAULT ACTION POWER You can decide what power to supply in case of broken probe. FAP is the reference power for parameter FAP. Average power is the average power calculated in the last 300 sec.
  • Page 57 The alarm is not activated if the control (Ctr) is ON/OFF type, during Selftuning and in Manual. 5 min. PF.t Process variable SP + b.St SP - b.St Power Average power + b.PF Average power Average power - b.PF Alarm power The parameters for alarm power are: 0.0 ...
  • Page 58: Softstart For Preheating

    SOFTSTART FOR PREHEATING This function lets you deliver a settable power (So.P) for time (SoF), after which normal control is resumed by means of PID control. Activation is only at switch-on, with manual-automatic switching during Softstart (the time restarts from 0), and if the process variable is below setpoint SP.S.
  • Page 59: Power Control

    POWER CONTROL SSR CONTROL MODES ON Modality The GFX4-IR has the following power control modes: - PA modulation via variation of phase angle - ZC, BF, HSC modulation via variation of number of conduction cycles with zero crossing trigger. PA phase angle: this mode controls power on the load via modulation of the phase angle.
  • Page 60 Model 30kW 60kW 80kW 15.0 30.0 60.0 FU. t A Max. limit of RMS current in normal op 0.0 ...999.9 A DIP5 = OFF (resistive load) bF. ( y Min. number of cycles in BF mode 1 ...10 DIP5 = ON (inductive load) NB: In case of a 3-phase load, you can set a different value from parameter FU.tA for each zone (ex.
  • Page 61 For non-linear loads (ex.: Super Kanthal or Silicon Carbide) the automatic calibration procedure IS NOT necessary. Set the value of parameters ref.V, ref. I, ref. P based on the specific nominal of the load shown on the data-sheet (ref. GFX4-IR In- stallation Guide).
  • Page 62 xd. 6 Enable feedback modes Table feedback modes None (Voltage) (Current) P (Power) None V (Linear voltage) I (Linear current) (OR. V 100.0 Maximum correction of voltage feedback 0.0 ...100.0 % 100.0 (OR. i Maximum correction of current feedback 0.0 ...100.0 % 100.0 (OR.
  • Page 63 HEURISTIC Control power It is useful to be able to limit the delivery of total power to the loads in order to avoid input peaks from the single-phase power line. This condition occurs during switch-on phases when the machine is cold; the demand for heating power is 100% until temperatures near the setpoint are reached.
  • Page 64 Table for enabling heuristic power power control ZONE 1 ZONE 2 ZONE 3 ZONE 4 NOTE: Only for GFX4-IR output OUT1 ...OUT4 with slower cycle time (1.200sec) all HEAT or all COOL. Maximum current for heuristic power I. X EU Heuristic power table control 0.0 ...
  • Page 65: Virtual Instrument Control

    VIRTUAL INSTRUMENT CONTROL Virtual instrument control is activated by means of parameter hd.1. By setting parameters S.In and S.Ou you can enable the writing of some parameters via serial line, set the value of inputs and the state of outputs. You have to enable alarm setpoints AL1, ..., AL4 when write operations are continuous, and you don’t have to keep the last value in eeprom.
  • Page 66: Hw/Sw Information

    At value SV on the GFX-OP display, the figures indicate the value of bits as follows: = 1 COOL OUTPUT triac 250Vac 1A - THOUSANDS and HUNDREDS (Power GFX4-IR) correspond to bits 7 to 9 - TENS (COOL outputs) correspond to bits 1 to 4 = 1 GFX4-IR 30 kW...
  • Page 67 3-phase load open delta OFF/ON 3-phase load closed delta 3-phase star load without neutral 3-phase star load with neutral 5000 Manufact - Trade Mark (Gefran) Name of the manufacture Device ID (GFX4-IR) Product identifier Ld. s t RN LED status function...
  • Page 68 Current instrument state (STATUS_W) Table of instrument settings Instrument state saved in eeprom (STATUS_W_EEP) Select SP1/SP2 Start/Stop Selftuning Select ON/OFF Select AUTO/MAN Start/Stop Autotuning Select LOC/REM Instrument state Table of instrument state AL.1 or AL.2 or AL.3 or AL.4 or or Power Fault ALHB.TA1 or ALHB.TA2 or ALHB.TA3 Input Lo...
  • Page 69 Instrument state 4 Table of instrument state 4 SSR Temperature sensor broken SSR Temperature sensor over heat phase_softstart_active phase_softstart_end frequency_warning or monophase_missing_line_warning 60Hz short_circuit_current in phase softstart over_peak_current in phase softstart over_ms_current in normal operation Voltage status Table of voltage status frequency_warning 10% unbalanced_line_warning 20% unbalanced_line_warning...
  • Page 70: Instrument Configuration Sheet

    INSTRUMENT CONFIGURATION SHEET PARAMETERS Assigned Definition of parameter Note value INSTALLATION OF MODBUS SERIAL NETWORK Instrument identification code Select Baudrate - Serial 1 bav. 2 Select Baudrate - Serial 2 Select parity - Serial 1 par. 2 Select parity - Serial 2 [.
  • Page 71 S. 0 8 Engineering value attributed to Point 8 S. 0 9 Engineering value attributed to Point 9 S. 1 0 Engineering value attributed to Point 10 S. 1 1 Engineering value attributed to Point 11 S. 1 2 Engineering value attributed to Point 12 S.
  • Page 72 LOAD CURRENT VALUE Offset correction CT input o. t A1 (phase 1) Offset correction CT input o. t A2 with three-phase load (phase 2) Offset correction CT input o. t A3 with three-phase load (phase 3) Instantaneous CT input value I.
  • Page 73 LINE VOLTAGE VALUE Offset correction voltmeter transformer o. t U1 input TV (phase 1) Offset correction voltmeter transformer o. t U2 with three-phase load input TV (phase 2) Offset correction voltmeter transformer o. t U3 with three-phase load input TV (phase 3) 1.
  • Page 74 DIGITAL INPUTS diG. Function of digital input diG. 2 Function of digital input 2 State of digital inputs INPUT DIG STATE OF DIGITAL OFF = Digital input 1 off INPUT 1 ON = Digital input 1 on STATE OF DIGITAL OFF = Digital input 2 off INPUT 2 ON = Digital input 2 on...
  • Page 75 GENERIC ALARMS AL1, AL2, AL3 and AL4 a1. r Select reference variable alarm 1 A2. r Select reference variable alarm 2 A3. r Select reference variable alarm 3 A4. r Select reference variable alarm 4 AL. 1 Setpoint alarm 1 (scale points) 475 - 177 AL.
  • Page 76 AL4 direct/inverse AL4 absolute/relative AL4 normal/symmetrical AL4 disabled at switch on AL4 with memory AL. n Select number of enabled alarms diG. Digital input function diG. 2 Digital input function 2 OFF = Reset alarm latch ON = Reset alarm latch STATE OF OFF = Alarm off ALARM 1...
  • Page 77 HB ALARM (Heater Break Alarm) AL. n Select number of enabled alarms Xb. f HB alarm function XB. T Delay time for HB alarm activation HB alarm setpoint (ammeter input scale A. x b1 with 3-phase load points - Phase 1) HB alarm setpoint (ammeter input scale A.
  • Page 78 ALARM SBR - ERR (Probe in short or connection error) Fault action (in case of broken probe) Sbr, Err Only for main input Fault action power fa. p (supplied in condition of broken probe) Self-diagnosis error code for main input OFF = - STATE OF INPUT IN SBR ON = Input in SBR...
  • Page 79 OUTPUTS State outputs rL.x MASKOUT OFF = Output off STATE rL.1 ON = Output on OFF = Output off STATE rL.2 ON = Output on OFF = Output off STATE rL.3 ON = Output on OFF = Output off STATE rL.4 ON = Output on OFF = Output off STATE rL.5...
  • Page 80 SETPOINT SETTINGS Local setpoint 16 - 472 tp. 2 Auxiliary analog input function Remote setpoint (SET Gradient for SP. r manual power correction) 136 - 249 SERIAL_SP Remote Setpoint from serial line Lowest settable limit SP, SP remote and Lo. L absolute alarms 20 - 28 - 142 Highest settable limit SP, SP remote and...
  • Page 81 PID HEAT/ COOL CONTROL Enable zone process variable Control type Proportional band for heating or h. p b hysteresis ON/OFF 148 - 149 h. 1 t Integral heating time h. d t Derivative heating time Proportional band for cooling or c.
  • Page 82 AUTOMATIC/MANUAL CONTROL MANUAL_POWER Value control outputs 0v. p (+Heat / -Cool) 132 - 471 diG. Digital input function diG. 2 Digital input function 2 OFF = Automatic AUTO/MAN ON =Manual Instrument state (STATUS_W) HOLD FUNCTION diG. Digital input function diG. 2 Digital input function 2 OFF = hold off HOLD...
  • Page 83 SELFTUNING Enable selftuning, s. t v autotuning, softstart diG. Digital input function diG. 2 Digital input function 2 OFF = Stop Selftuning SELFTUNING ON = Start selftuning OFF = Selftuning in Stop SELFTUNING STATE ON = Selftuning in Start DIGITAL INPUT OFF = Digital input 1 off STATE 1 ON = Digital input 1 on...
  • Page 84 POWER ALARM Stability band b. s t (hot runners power alarm function) Power alarm band b. p f (hot runners power alarm function) Power alarm delay time pf. t (hot runners) rL. 1 Allocation of reference signal rL. 2 Allocation of reference signal Allocation of reference signal rL.
  • Page 85 DELAY TRIGGERING Delay triggering dL. T (first trigger only) Minimum non-conduction time to dL. O F reactivate delay triggering FEEDBACK MODES Xd. 6 Enable feedback modes (or. U Maximum correction of voltage feedback (or. i Maximum correction of current feedback (or.
  • Page 86 UPD. F Fieldbus software version (od. F Fieldbus node bAU. F Fieldbus baudrate State of jumper Manufact - Trade Mark (Gefran) Device ID (GFX4-IR) Ld. s t RN status LED function Ld. 2 ER status LED function Ld. 3 DI1 LED function Ld.
  • Page 87 Notes 80415F_MSW_GFX4-IR_05-2019_ENG...
  • Page 88 GEFRAN spa via Sebina, 74 25050 Provaglio d’Iseo (BS) Italy Tel. +39 0309888.1 Fax +39 0309839063 info@gefran.com http://www.gefran.com...

Table of Contents