gefran GFW 400-600A Configuration And Programming Manual

gefran GFW 400-600A Configuration And Programming Manual

Modular power controller
Hide thumbs Also See for GFW 400-600A:

Advertisement

Quick Links

This document supplements the following manuals:
- Instructions and warnings for GFW
80997D_MSW_GFW_400-600_04-2021_ENG
GFW 400-600A
MODULAR POWER CONTROLLER
CONFIGURATION AND
PROGRAMMING MANUAL
Software version: 1.0x
code: 80997D - 04-2021 - ENG
ATTENTION!
This manual is intended for technical person-
nel, who commission the instrument by connecting
it to other units, and for service and maintenance
personnel.
It is assumed that such persons have adequate
technical knowledge, especially in the fields of elec-
tronics and automation.
The instrument described in this manual may
be operated only by personnel who are trained for
their assigned task, in conformity to the instructions for
such task and, specifically, to the safety warnings and
precautions contained in such instructions.
Thanks to their training and experience, quali-
fied personnel can recognize the risks inherent to the
use of these products/systems and are able to avoid
possible dangers.
The Customer is obligated to respect trade
secrets. Therefore, this manual and its attachments
may not be tampered with, changed, reproduced,
or transferred to third parties without GEFRAN's
authorization.
1

Advertisement

Table of Contents
loading

Summary of Contents for gefran GFW 400-600A

  • Page 1 The Customer is obligated to respect trade secrets. Therefore, this manual and its attachments may not be tampered with, changed, reproduced, or transferred to third parties without GEFRAN’s authorization. 80997D_MSW_GFW_400-600_04-2021_ENG...
  • Page 2 80997D_MSW_GFW_400-600_04-2021_ENG...
  • Page 3: Table Of Contents

    TABLE OF CONTENTS AND SUMMARIES INTRODUCTION ...............4 CONTROLS ..............49 FIELD OF USE ...............4 AUTOMATIC / MANUAL CONTROL ......51 CHARACTERISTICS OF PERSONNEL ......4 MANUAL POWER CORRECTION .......52 STRUCTURE OF THIS MANUAL ........5 START MODE ...............52 SOFTWARE SHUTDOWN ..........53 INSTRUMENT ARCHITECTURE ........6 SERIAL COMMUNICATION (MODBUS) ......7 OTHER FUNCTIONS ............54 CONNECTION ..............8...
  • Page 4: Introduction

    RS485, with specific GF_eXpress application software. Since it is impossible to foresee all of the installations and environments in which the instrument may be applied, adequate technical preparation and complete knowledge of the instrument’s potentials are necessary. GEFRAN declines all liability if rules for correct installation, configuration, and/or programming are disregarded, as well as all liability for systems upline and/or downline of the instrument.
  • Page 5: Structure Of This Manual

    This manual was originally written in ITALIAN. Therefore, in case of inconsistencies or doubts, request the original manual or explanations from GEFRAN. The instructions in this manual do not replace the safety instructions and the technical data for installation, configu- ration and programming applied directly to the product or the rules of common sense and safety regulations in effect in the country of installation.
  • Page 6: Instrument Architecture

    INSTRUMENT ARCHITECTURE The modular power controller’s flexibility permits replacement of previous-version such as GEFLEX (GFX), GFX4 and GFX4-IR instruments without changing the control software in use. Based on the chosen work mode (see MODBUS SERIAL COMMUNICATION), you can use the instrument in 2 different modes: - GFX compatible mode: as if there were at most 3 separate instruments (recommended for retrofitting projects and/ or replacement of damaged instruments);...
  • Page 7: Serial Communication (Modbus)

    SERIAL COMMUNICATION (MODBUS) There are two Modbus addressing modes for variables and configuration parameters: - GFX compatible - GFX4/GFW The modes are selected with dip-switch-7. GFX-compatible mode (dip-switch-7 =ON) This lets you uses supervision programs created for Geflex modules. Memory is organized in at most 3 groups: Zone 1 for the variables of the module GFW-M Zone 2 for the variables of the module GFW-E1 Zone 3 for the variables of the module GFW-E2...
  • Page 8: Connection

    Serial communication time constraints in Modbus RTU The following time constraints must be complied with in order to allow correct serial data exchange with the device: Reading Word/Register parameters: Reading N consecutive parameters, with N from 1 to 16, requires a time of almost 50 ms. In this case the following read and write Modbus command, to the same node, must be sent after this interval time.
  • Page 9 Installation of the “MODBUS” serial network A network typically has a Master that “manages” communication by means of “commands” and Slaves that interpret these commands. GFW are considered Slaves to the network master, which is usually a supervision terminal or a PLC. They are positively identified by means of a node address (ID) set on the rotary switches (tens + ones).
  • Page 10: Inputs

    INPUTS IN.A1/IN.A2/IN.A3 ANALOG INPUTS The modular power controller has three analog inputs with the functionality of power control. Probe type Analog input 1 tP.A1 Table of analog input Disable 0...10V tP.A2 Analog input 2 0...5V / Potentiometer 0...20mA tP.A3 Analog input 3 4...20mA Scale limits Minimum scale limit LS.A1...
  • Page 11 Ou .P P.V. Example: 100.0 % H S.A = 100.0 = 2…10V Since the 0…10V input range is reduced 80% above, the scale interval (HS.A – LS.A) must be extended downward so that the tyP. = 1 useful interval (100.0 – 0.0) is 80% (100.0/125.0 = 0.8). LS.A1 = -25.0 0.0 % HS.A1 = 100.0...
  • Page 12 FUNCTIONAL DIAGRAM analog input value (In.A1) Probe type Scale limits Low pass filter Input signal HS.A1, LS.A1 FLt.A1 tP.A1 see Control analog input value (In.A2) Scale limits Low pass filter Probe type Input signal tP.A2 HS.A2, LS.A2 FLt.A2 see Control analog input value (In.A3) Probe type...
  • Page 13: Current Value In Load

    CURRENT VALUE IN LOAD The RMS current value is read in variable Ld.A of each zone. If zone 1 has a 3-phase load, variable Ld.At contains the average value of the three RMS currents. The Ld.A of the first three zones contain the RMS current value on lines L1, L2 and L3, respectively..
  • Page 14 Setting the offset -99.9 ...99.9 Offset correction CT input 220* o.tA1 Zone 1 Zone 2 Zone 3 (phase 1) scale points -99.9 ...99.9 Offset correction CT input o.tA2 (phase 2) scale points -99.9 ...99.9 Offset correction CT input o.tA3 (phase 3) scale points external CT Offset correction for external...
  • Page 15 FUNCTIONAL DIAGRAM Monophase load (Instantaneous current) (ON current) (Load RMS current) Variable Variable Variable Limiti di scala, I.tA1 I.tA1 Low pass Function I.1ON Ld.A Management: Offset value auxiliary filter (Ou.P) Variable - HB Alarm (o.tA1) SCR ON input (Ft.tA) I.tAP - No Current Alarm - Feedback I (Peak current)
  • Page 16: Voltage Value On Load

    VOLTAGE VALUE ON LOAD RMS voltage is read in variable Ld.V of each zone. If zone 1 has a 3-phase load, variable Ld.V.t in the first zone contains the average RMS value of voltages on three load L1, L2 and L3. Voltage on the load is acquired with sampling on each cycle, 20ms at 50Hz (16.6ms at 60Hz).
  • Page 17 FUNCTIONAL DIAGRAM Single-Phase Load without VLOAD option Variable Ld.V Voltmeter input phase1 I.VF1 Control value output Ou.P Single-Phase Load with VLOAD option Variabile Ld.V Offset Offset Voltmeter input scale limits scale limits on the load (o.tVL) (Ft.tVL) phase FUNCTIONAL DIAGRAM Three-Phase Load without VLOAD option Variable Ld.V phase 1 Voltmeter input...
  • Page 18 Three-Phase Load with VLOAD option Variabile Ld.V phase 1 Scale limits, Filter Voltmeter input on the load Offset low pass phase 1 (o.tVL zone 1) (Ft.tVL zone 1) Variabile Ld.V phase 2 Scale limits, Filter Voltmeter input on the load Offset low pass phase 2...
  • Page 19: Line Voltage Value

    LINE VOLTAGE VALUE There are the following parameters if zone 1 has a single-phase load: I.tV1 instantaneous voltmeter value of line I.VF1 filtered voltmeter value o.tV1 voltmeter input offset correction Ft.tV voltmeter input digital filter There are the following parameters if zone 1 has a 3-phase load: I.tV1, I.tV2 and I.tV3, the instantaneous voltmeter value on line L1, L2 and L3, respectively.
  • Page 20 Read state Value of voltmeter input 232* 1.tU1 (phase 1) Value of voltmeter input 1.tU2 With 3-phase load (phase 2) Value of voltmeter input 1.tU3 With 3-phase load (phase 3) Value filtered of voltmeter input 322* 1.VF1 (phase 1) Value filtered of voltmeter input 1.VF2 With 3-phase load (phase 2)
  • Page 21 FUNCTIONAL DIAGRAM Single-phase load Variable I.VF1 Scale limits, Filter Voltmeter see generic low pass Offset input alarms (o.tV1) (Ft.tV) phase1 Variable I.tV1 FUNCTIONAL DIAGRAM 3-phase load Scale limits, Filter Voltmeter Variable I.VF1 low pass Offset input (o.tV1) (Ft.tV) phase1 Variable I.tV1 Filter Scale limits, Voltmeter...
  • Page 22: Power On Load

    POWER ON LOAD Power on the load in each zone is read in variable Ld.P and the corresponding energy value in variables Ld.E1 and Ld.E2. These energy values show the value accumulated since the first power on or since the last reset (commands at bits 114 and 115); non-volatile memory is updated every two hours and the disconnection of the power off.
  • Page 23 FUNCTIONAL DIAGRAM Single-phase load RMS voltage value on load (Ld.V) Variables Ld.E1 Variable Ld.P and Ld.E2 by time X CoS.F active power [kW] energy [kwh] RMS current value on load (Ld.A) Variable Ld.I Ld.V/Ld.A impedance [ohm] FUNCTIONAL DIAGRAM 3-phase load Variable Ld.E1 and Ld.E2 phase 1 Variable Ld.P phase 1 for time...
  • Page 24: Digital Inputs

    DIGITAL INPUTS There are always four inputs. Each input can perform various functions based on the setting of the following parameters: diG.1 Digital input 1 function Digital input functions table Activation Digital input 2 function diG.2 No functions (input off) On leading edge MAN / AUTO controller On leading edge diG.3...
  • Page 25 ADVANCED SETTINGS NOTE: if the digital input is used to command the power % (Ou.P) on the load (PWM input function, diG = 7), it is important to set Timeout parameter PWm.t to a value equal to or higher than the period of the PWM control signal used to guarantee this reaction time even in static conditions of low input (Ou.P=0%) or high input (Ou.P=100%).
  • Page 26: Using A Function Associated With Digital

    USING A FUNCTION ASSOCIATED WITH DIGITAL INPUT AND VIA SERIAL At power-on or on the leading edge of digital input 1 or 2, all zones assume the state set by the digital input. For each zone, this state can be changed by writing via serial. The setting via serial is saved in eeprom (STATUS_W_EEP, address 698).
  • Page 27: Using A Function Of Digital Input 1 To Enable At

    USING A FUNCTION OF DIGITAL INPUT 1 TO ENABLE AT SOFTWARE ON Software ON can be configured either by enabling a digital input or by writing via serial. Enabling by digital input 1 (diG) is common to all zones, whereas enabling via serial is specific for each individual zone. The ON/OFF setting via serial is saved in eeprom (STATUS_W_EEP, address 698 bit 3) for resetting of the condition at the next hardware power-on;...
  • Page 28: Alarms

    ALARMS GENERIC ALARMS AL1, AL2, AL3 and AL4 Four generic alarms are always available and can perform various functions. Typically, alarm AL.1 is defined as minimum and AL.2 as maximum. These alarms are set as follows: - select the reference variable to be used to monitor the value (parameters A1.r, A2.r, A3.r and A4.r): the source of this variable can be selected from among the ammeter input, voltmeter input, and analog input.
  • Page 29 Reference variables Select reference variable 215* a1.r Table of alarm reference setpoints Zone 1 Zone 2 Zone 3 alarm 1 Reference Variable to be compared Select reference variable setpoint 216* A2.r Zone 1 Zone 2 Zone 3 alarm 2 In.tA1 (In.tA1 OR In.tA2 OR In.tA3 with 3-phase load)) In.tV1 (In.tV1 OR In.tV2 OR Select reference variable...
  • Page 30 Alarm type 406* Alarm type 1 a1.t Table of alarm behaviour Zone 1 Zone 2 Zone 3 Direct Normal 407* Alarm type 2 (high limit) Absolute Zone 1 Zone 2 Zone 3 Symmetrical Inverse Relative (window) (low limit) 408* a3.t Alarm type 3 Direct Absolute Normal...
  • Page 31 AL4 normal/symmetrical AL4 disabled at switch-on AL4 with memory Enable alarms Select number of enabled 195* AL.n Table of enabled alarms alarms Zone 1 Zone 2 Zone 3 Alarm 1 Alarm 2 Alarm 3 Alarm 4 disable disable disable disable enabled disable disable...
  • Page 32 Read state OFF = Alarm OFF State of alarm ON = Alarm ON State of alarm OFF = Alarm OFF ON = Alarm ON OFF = Alarm OFF State of alarm ON = Alarm ON 69 * State of alarm OFF = Alarm OFF ON = Alarm ON 318*...
  • Page 33 FUNCTIONAL DIAGRAM Alarm setpoint Type of alarm and State of alarm AL1 hysteresis (A1.t, HY.1) Type of alarm and Alarm setpoint State of alarm AL2 hysteresis (A2.t, HY.2) See outputs Type of alarm and Alarm setpoint State of alarm AL3 hysteresis (A3.t, HY.3) Alarm setpoint...
  • Page 34: Hb Alarm (Heater Break Alarm)

    HB ALARM (Heater Break Alarm) This type of alarm identifies load break or interruption by measure the current delivered by means of a current transformer. The following three fault situations may occur: - delivered current is lower than nominal current: this is the most common situation, and indicates that a load element is breaking. - delivered current is higher than nominal current: this situation occurs, for example, due to partial short circuits of load elements.
  • Page 35 Maximum conduction value in this phase can be limited by means of the PS.Hi parameter. If requested, MUST be activated only with Hd.6=0 (the required Hd.6 value can be set only after calibration). In case of HSC firng mode, the Heater Break alarm teach-in function doesn’t calibrate at 5%, 3%, 2% and 1% in order to avoid high peak currents due to the low impedence at very low temperature of the IR lamp filament.
  • Page 36 HB Calibration with IR lamp: 759* Ir.tA.1 0.0...3275.0 A Zone 1 Zone 2 Zone 3 current at 50% conduction HB Calibration with IR lamp: 760* 0.0...3275.0 A Ir.tA.2 Zone 1 Zone 2 Zone 3 current at 30% conduction HB Calibration with IR lamp: 761* Ir.tA.3 0.0...3275.0 A...
  • Page 37 Read state HB alarm setpoint as function 744* xb.tr of power on load HB ALARM OFF = Alarm OFF STATE OR PO- ON = Alarm ON WER_FAULT State of HB OFF = Alarm OFF alarm phase ON = Alarm ON State of HB OFF = Alarm OFF alarm phase...
  • Page 38 HB Calibration in modes ZC - BF - HSC Ou.P power in Value of Ou.P Hb.Pw control outputs calibration CT read in HB alarm Value of CT input HB calibration setpoint with output on (phase 1) A.Hb Hb.TA I.1ON Percent HB alarm setpoint of current read in HB calibration Hb.P...
  • Page 39 Power Fault ALARMS (SSR_SHORT, NO_VOLTAGE and NO_CURRENT) Enable POWER_FAULT 660* hd.2 Table of Power Fault alarms Zone 1 Zone 2 Zone 3 alarms SSR _SHORT NO_ VOLTAGE NO_ CURRENT + 32 alarms with memory + 136 enables partial load mode (128+8) for three-phase delta configuration without neutral, with or without transformer Y/Y or Δ...
  • Page 40 State of alarm OFF = Alarm OFF with 3-phase load NO_CURRENT ON = Alarm ON phase 3 OVERHEAT ALARM Each power module has one temperature sensor for the internal heat sink and two additional temperature sensors connected to the LINE and LOAD terminals. Temperature levels are shown in variables INNTC_SSR, INNTC_LINE and INNTC_LOAD.
  • Page 41 634* State 4 (STATUS4) Table state 4 80997D_MSW_GFW_400-600_04-2021_ENG...
  • Page 42: Outputs

    OUTPUTS The modular power controller has high flexibility in the assignment of functions to the physical outputs. As a result, the instrument can be used in sophisticated applications. A function is assigned to each physical output in two steps: first assign the function to one of internal reference signals rL.1 .. rL.6, and then attribute the reference signal to parameters out.1 ..
  • Page 43: Allocation Of Reference Signals

    ALLOCATION OF REFERENCE SIGNALS 160* rL.1 Allocation of reference signal Table of reference signals Zone 1 Zone 2 Zone 3 163* rL.2 Allocation of reference signal Function Zone 1 Zone 2 Zone 3 Ou.P (control output) AL1 - alarm 1 AL2 - alarm 2 AL3 - alarm 3 NOTE: Parameters rL.1, ..., rL.6 for each zone can be consi- dered as internal states.
  • Page 44 Allocation of reference 166* rL.3 Zone 1 Zone 2 Zone 3 signal Function AL1 - alarm 1 Allocation of reference 170* rL.4 Zone 1 Zone 2 Zone 3 signal AL2 - alarm 2 Allocation of reference AL3 - alarm 3 171* rL.5 Zone 1...
  • Page 45 1 ...200 sec. 159* (t.2 OUT 2 cycle time Zone 1 Zone 2 Zone 3 (0.1 ...20.0 sec.) 80997D_MSW_GFW_400-600_04-2021_ENG...
  • Page 46 Read state 308* State rL.x (MASKOUT_RL) Table of signal reference states 319* State rL.1 State rL.2 State rL.3 State rL.4 State rL.5 State rL.6 OFF = Signal Off STATE rL.1 ON = Signal On OFF = Signal Off STATE rL.2 ON = Signal Ono OFF = Signal Off STATE rL.3 ON = Signal On...
  • Page 47 Read state State of output OFF = Output Off OUT1 ON = Output On State of output OFF = Output Off OUT2 ON = Output On State of output OFF = Output Off OUT3 ON = Output On State of output OFF = Output Off OUT5 ON = Output On...
  • Page 48 FUNCTIONAL DIAGRAM Ou.P rL.1 - Zone1 State of AL1 rL.2 - Zone1 State of AL2 Allocation State of AL3 of reference State of AL4 signal rL.3 or rL.5 - Zone1 (rL.1, rL.2, State of Hb.1 rL.3, rL.4, rL.5, rL.6) State of Hb.2 (*) rL.4 or rL.6 - Zone1 State of Hb.3 (*) Out1...
  • Page 49: Analog Outputs

    ANALOG OUTPUTS The 3 optional analog outputs let you retransmit the value of analog quantities. The engineering value of the quantity is limited to the set scale values and a reparameterization is applied based on the type of output selected. Exemple 1: To retransmit the current of the GFW-M load with range 0 –...
  • Page 50 Minimum scale limit of analog Scale Min...max based on reference s ls.A01 output 1 elected in rF.AO1 Minimum scale limit of analog Scale Min...max based on reference ls.A02 output 2 selected in rF.AO2 Minimum scale limit of analog Scale Min...max based on reference ls.A03 output 3 selected in rF.AO3...
  • Page 51: Controls

    CONTROLS Parameters Reference power Table of selection Zone 1 Zone 2 Zone 3 Power from analog input 1 (In.A1) Power from digital input 1 (In.Pwm1) Power from GFW-M (FW_POWER) (**) Power from GFW-E1 (FW_POWER) (**) Power from GFW-E2 (FW_POWER) (**) Power from analog input 2 (In.A2) Power from analog input 3...
  • Page 52 FUNCTIONAL DIAGRAM Analog input 1 (In.A1) Analog input 2 (In.A2) Status_W diG1 Analog input 3 P.PEr P.oFS diG.2 (In.A3) diG.3 diG.4 Digital input 1 (In.Pwm1) Lo.P POWER Power AUTO reference Digital input 2 (SPU) (In.Pwm2) MANUAL_POWER Digital input 3 (In.Pwm3) Power from GFW-M (FW_POWER) Power from GFW-E1...
  • Page 53: Automatic / Manual Control

    AUTOMATIC / MANUAL CONTROL By means of the digital input function you can set the controller in MAN (manual) and set the control output to a constant value changeable by means of communication. When returning to AUTO (automatic), if the variable is within the proportional band, switching is bumpless. 252* MANUAL_POWER -100.0...100.0%...
  • Page 54: Manual Power Correction

    MANUAL POWER CORRECTION With this function you can run a correction of power delivered in manual based on the reference line voltage (riF). The % value of the (Cor) is freely settable and acts in inverse proportion. The function is activated/deactivated by means of parameter SP.r. Example: with the following settings: Cor = 10%;...
  • Page 55: Software Shutdown

    SOFTWARE SHUTDOWN Running the software shutdown procedure causes the following: 1) Digital input enabled only if assigned to SW shutdown function. 2) Outputs OFF: except for signals them of reference rL.4 and rL.6 that they come forced ON 3) Reset of HB alarm. 4) Alarms AL 1…...
  • Page 56: Other Functions

    OTHER FUNCTIONS HEATING OUTPUT (Fast cycle) For output rL.1 (corresponding to physical output Out 1), you can set a fast cycle time (0.1 ... 20.0 sec.) by setting parameter rL.1 to 64 (Ou.P function). DIP 5 = OFF (Resistive load) 1...200 sec.
  • Page 57: Power Control

    POWER CONTROL SSR CONTROL MODES ON Modality The GFW has the following power control modes: PA modulation via variation of phase angle - ZC, BF, HSC modulation via variation of number of conduction cycles with zero crossing trigger. PA phase angle: this mode controls power on the load via modulation of the phase angle. ZC zero crossing: this type of operation reduces EMC emissions.
  • Page 58 Table of trigger modes Ramp Trigger mode Current Ramp Trigger mode Current in normal mode in softstart control in normal mode in softstart control Softstart operation in normal Softstart operation in normal operationt operation ZC/BF ZC/BF ZC/BF ZC/BF ZC/BF ZC/BF ZC/BF ZC/BF ZC/BF...
  • Page 59 SOFTSTART or START RAMP This type of start can be enabled either in phase control or pulse train mode and acts via control of the conduction angle. It is enabled with parameter Hd.5. The softstart ramp starts from a zero conduction angle and reaches the angle set in parameter PS.HI in the time set in parameter PS.tm, from 0.1 to 60.0 sec.
  • Page 60: Feedback Modes

    DELAY TRIGGERING In firing modes ZC and BF, with inductive loads, this function inserts delay triggering in the first cycle. The delay is expressed in degrees settable in parameter dL.t, from 0 to 90 degrees. ◊ Optimised Delay-Triggering value for transformer monophase: 60° ◊...
  • Page 61 IMPORTANT Feedback calibration can be activated from the digital input (parameters diG.1/diG.2/diG.3/diG.4) or by serial control (ref. bit113), and if re- quested MUST be activated only with Hd.6=0 (the required Hd.6 value can be set only after calibration) and preferably with maximum power on the load (ex.
  • Page 62 Read state Setpoint of V, I, P to maintain on load 886* 757* ARif Reference of Feedback 0.0 ...999.9 V Data in DWORD (32 bit) format for address 886* LSW only LSW data in WORD (16 bit) format for address 757* 0.0 ...
  • Page 63: Heuristic Control Power

    HEURISTIC CONTROL POWER It is useful to be able to limit the delivery of total power to the loads in order to avoid input peaks from the single-phase power line. This condition occurs during switch-on phases when the machine is cold; the demand for heating power is 100% until temperatures near the setpoint are reached.
  • Page 64: Heterogeneous Power Control

    Enable heuristic hd.3 Table for enabling heuristic power power control Zone1 Zone1 Zone2 Zone2 Zone3 Zone3 NOTE: Only for GFW with CTs present and outputs OUT1...OUT3 with slow cycle time (1...200 sec.) Maximum current for I.XEU 0.0…3275.0 A heuristic power control HETEROGENEOUS POWER CONTROL This function matches that of a thermal cutout that disconnects the load based on instantaneous input.
  • Page 65: Virtual Instrument Control

    VIRTUAL INSTRUMENT CONTROL Virtual instrument control is activated by means of parameter hd.1. By setting parameters S.In and S.Ou you can enable the writing of some parameters via serial line, set the value of inputs and the state of outputs. You have to enable alarm setpoints AL1, ..., AL4 when write operations are continuous, and you don’t have to keep the last value in eeprom.
  • Page 66: Hw/Sw Information

    Led ER word, bit 1 SERIAL_LEDS Led D1 word, bit 2 SERIAL_LEDS Led D2 word, bit 3 SERIAL_LEDS Led O1 word, bit 4 SERIAL_LEDS Led O2 word, bit 5 SERIAL_LEDS Led O3 word, bit 6 SERIAL_LEDS Led BUT word, bit 7 SERIAL_LEDS Input D1 word, bit 10...
  • Page 67 = 1 GFW-E1 no power = 1 GFW-E1 200A = 1 GFW-E1 400A = 1 GFW-E1 600A = 1 GFW-E2 no power = 1 GFW-E2 200A = 1 GFW-E2 400A = 1 GFW-E2 600A Upd.F Fieldbus software version Fieldbus node (od.F Fieldbus baudrate Profibus...
  • Page 68 3-phase load closed delta 3-phase star load without neutral 3-phase star load without neutral with BIFASE control 3-phase closed star load with BIFASE control Name of manufacturer Manufact - Trade Mark (Gefran) 5000 Product ID Device ID (GFW600A) Ld.st RN LED status function...
  • Page 69 State saved in eeprom 698* (STATUS_W_EEP) zone1 zone2 zone3 467* State (STATUS) Table of state AL.1 or AL.2 or AL.3 or AL.4 or ALHB.TA1 or ALHB.TA2 or ALHB.TA3 or POWER_FAULT Ou.P > 0 ALHB or POWER_FAULT ON/OFF AUTO/MAN 469* State 1 (STATUS1) Table of state 1 AL.1 or AL.2 or AL.3 or AL.4 or ALHB.TA1 or ALHB.TA2 or ALHB.TA3 or POWER_FAULT...
  • Page 70 Voltage status Table voltage status frequency_warning 10% unbalanced_line_warning 20% unbalanced_line_warning 30% unbalanced_line_warning rotation123_error three-phase_missing_line_error 60Hz Device not ready Functionality key 80997D_MSW_GFW_400-600_04-2021_ENG...
  • Page 71: Instrument Configuration Sheet

    Ready for Normal pressed pressed Calibration HB alarm operation calibration HB alarm > 3 sec. (*) > 3 sec. (*) LED RN (green) flashing LED RN (green) steadily on LED RN (green) flashing rapidly LED BUT (yellow) off LED BUT (yellow) 1 flash every second..
  • Page 72 INPUTS ANALOG INPUT tP.A1 Analog input 1 tP.A2 Analog input 2 tP.A3 Analog input 3 Minimum scale limit LS.A1 analog input 1 Minimum scale limit LS.A2 analog input 2 Minimum scale limit LS.A3 analog input 3 Maximum scale limit KS.A1 analog input 1 Maximum scale limit KS.A2...
  • Page 73 Offset correction CT input 220* o.tA1 (phase 1) Offset correction CT input o.tA2 (phase 2) Offset correction CT input o.tA3 (phase 3) Offset correction for external CT 393* r.tA input 227* Instantaneous CT input value I.ta1 473*- 139*- (phase 1) 756* Instantaneous CT input value I.ta2...
  • Page 74 Minimum limit of TV voltmeter L.t 3 input scale (phase 3) Maximum limit of TV voltmeter 410* K..t 1 input scale (phase 1) Maximum limit of TV voltmeter K..t 2 input scale (phase 2) Maximum limit of TV voltmeter K..t 3 input scale (phase 3) Digital filter TV auxiliary input 412*...
  • Page 75 Digital low-pass filter FT.P W m 2 input PWM 2 Digital low-pass filter FT.P W m 3 input PWM 3 OFF = Digital input 1 off STATE OF DIGI- ON = Digital input 1 on TAL INPUT OFF = Digital input 2 off STATE OF DIGI- ON = Digital input 2 on TAL INPUT...
  • Page 76 AL1 direct/inverse AL1 absolute/ relative AL1 normal/ symmetrical AL1 disabled at switch-on AL1 with memory AL2 direct/inverse AL2 absolute/ relative AL2 normal/sym- metrical AL2 disabled at switch-on AL2 with memory AL3 direct/inverse AL3 absolute/ relative AL3 normal/sym- metrical AL3 disabled at switch-on AL3 with memory AL4 direct/inverse...
  • Page 77 diG..4 Digital input function 4 Reset alarm latch OFF = Alarm off State of alarm 1 ON = Alarm on OFF = Alarm off State of alarm 2 ON = Alarm on OFF = Alarm off State of alarm 3 ON = Alarm on OFF = Alarm off State of alarm 4...
  • Page 78 HB Calibration with IR lamp: 383* Ir.tA.8 current at 2% conduction HB Calibration with IR lamp: 384* Ir.tA.9 current at 1% conduction HB Calibration with IR lamp: 445* Ir.tv0 voltage at 100% conduction HB Calibration with IR lamp: 446* Ir.tv1 voltage at 50% conduction HB Calibration with IR lamp: 447*...
  • Page 79 State of alarm OFF = Alarm off SSR_SHORT ON = Alarm on phase 1 State of alarm OFF = Alarm off SSR_SHORT ON = Alarm on phase 2 State of alarm OFF = Alarm off SSR_SHORT ON = Alarm on phase 3 State of alarm OFF = Alarm off...
  • Page 80 172* rL.6 Allocation of reference signal 152* (t.1 OUT 1 cycle time 159* (t.2 OUT 2 cycle time 308* State rL.x (MASKOUT_RL) 319* OFF = Signal off STATE rL.1 ON = Signal on OFF = Signal off STATE rL.2 ON = Signal on OFF = Signal off STATE rL.3 ON = Signal on...
  • Page 81 OFF = Output off State of output OUT8 ON = Output on OFF = Output off State of output OUT9 ON = Output on OFF = Output off State of output OUT10 ON = Output on State rL.x (MASKOUT_OUT) ANALOG OUTPUT tP.A01 Analog Output Type 1 tP.A02...
  • Page 82 766* p.OFS Offset of output power 763* G.OUT Gradient for output control 764* L.OP Minimum ignition output AUTOMATIC/MANUAL CONTROL 252* MANUAL_POWER 0v.p Value control outputs 132* - 471* diG.1 Digital input function 1 diG.2 Digital input function2 diG.3 Digital input function 3 diG.4 Digital input function 4 OFF = Automatic...
  • Page 83 HEATING OUTPUT (fast cycle) 160* rL.1 Allocation of reference signal 152* (t.1 OUT1 cycle time OPERATING HOUR METER 396* 0K.c hours of operation TRIGGER MODE SSR TRIGGER MODE 703* xd.5 Enable trigger modes Maximum limit of RMS current at 707* FU.tA normal operation Minimum number of cycles of...
  • Page 84 Fieldbus node (od.F Fieldbus baudrate bAu.F F.SIZ E I/O dimension for fieldbus State of jumper Manufact - Trade Mark (Gefran) Device ID (GFW600A) Ld.st RN status LED function Ld.2 ER status LED function DI1 status LED function Ld.3 DI2 status LED function Ld.4...
  • Page 85 Ld.5 O1 status LED function Ld.6 O2 status LED function Ld.7 O3 status LED function Ld.8 BUTTON status LED function 305* State (STATUS_W) State saved in eeprom 698* (STATUS_W_EEP) 467* State (STATUS) 469* State 1 (STATUS1) 632* State 2 (STATUS2) 633* State 3 (STATUS3) 634*...
  • Page 86 KEYPAD USE This charter describes the optional GFW-OP keypad and use mode to display and program parameters: ⇐ Signal led ⇐ Liquid crystal display 5 alphameric lines of 21 characters each ⇐ Pad keypad Description The program keypad is used to display the state and diagnostic parameters during operating period; on the back is present a ma- gnetic material strip to fix it on GFW-master frontal or on a metal surface (ex.
  • Page 87 Leds meaning: LEDs COLOUR MEANING Yellow Led is on when GFW is OFF software Yellow Led is on when GFW is in manual operating Green Led is on when during power supply This led flashes when GFW reaches a current limit condition (if enabled). ILIM During normal operation this led is off.
  • Page 88 Navigation Scan first and second level menus with the ▲, ▼, ◄ and ► keys: 80997D_MSW_GFW_400-600_04-2021_ENG...
  • Page 89 Scanning parameters You can access the following parameters by scanning first or second level menus: Displaying a parameter Indication of menu and position of parameter Modbus address of parameter (node – 16-bit address or 1-bit address) Description of parameter Depends on type of parameter: −...
  • Page 90 Changing a numerical parameter To change a numerical parameter (only if R/W): − Press the E key when the parameter to be changed is displayed. − The cursor (with inverted colors) is activated on the number corresponding to the unit. −...
  • Page 91 Changing a status parameter To change a state parameter (COMMANDS menu): - Press the E key when the parameter to be changed is displayed. - A description of the current state (with inverted colors) is displayed. - Press the ▲ and ▼ keys to switch the state among the available ones. - Press E again to save the value of the parameter after it is changed.
  • Page 92 Resetting alarms There are two types of alarms: 1) ALARMS WITH LATCH To reset an alarm with latch, go to the ALARM page that shows details of the alarm to be reset and press the ACK key: - if the cause of the error is no longer active, the corresponding message is deleted from the alarms list - if the cause of the error is still active, the corresponding message remains on the alarms list 2) ALARMS WITHOUT LATCH These are automatically reset when the cause of the error is removed.
  • Page 93 GEFRAN spa via Sebina, 74 25050 Provaglio d’Iseo (BS) Italy Tel. +39 0309888.1 Fax +39 0309839063 info@gefran.com http://www.gefran.com...

Table of Contents