3.33. Heterogeneous Power Control; Enabling Heterogeneous Power Control; Maximum Current For Heterogeneous Power Control - gefran GPC Configuration And Programming Manual

Advanced power controller
Table of Contents

Advertisement

3.33. Heterogeneous power control

The Heterogenous power control function is like a program-
mable circuit breaker. It allows the user to set a maximum
power to be used by the device in its entirety. If the maxi-
mum is reached then specific parts of the load are switched
off (disconnected) according to a predefined priority.
3.33.1.

Enabling heterogeneous power control

Address
Format
Single-
Multi-
node
node
1706
682
16 bit
The parameter enables heterogeneous power control of GPC-M, GPC-E1 and GPC-E2. Setting hd.4 = 0 disables heterogeneous power
control for all modules.
Options:
3.33.2.

Maximum current for heterogeneous power control

Address
Format
Single-
Multi-
node
node
1707
683
16 bit
The parameter sets the maximum current for heterogeneous power control.
min...max:
0.0...3275.0
GPC-OP
Acronym
menu
09.08.01
hd.4
Global
Index
0
1
2
3
4
5
6
7
GPC-OP
Acronym
menu
09.08.02
I.HEt
Global
81901A "MSW_GPC-40/600A"_03-2021_ENG_page 121
GPC-M always has priority and is switched off last. If power
control is enabled for several modules, the disconnection
sequence starts with the module with the highest number
(GPC-E2 before GPC-E1 and GPC-M, GPC-E1 before
GPC-M).
GF_eXpress menu
Description
MainMenu → Global → Powers → hd.4
GPC-M
GPC-E1
enabled
enabled
GF_eXpress menu
Description
MainMenu → Global → Powers → I.HEt
Unsigned
R/W
GPC-E2
enabled
R/W
(####.#)
0
Short
Float
A
0.0

Advertisement