Functions Of Indicator Leds; Control Connectors - gefran GTF-Xtra Installation And Operation Manual

Power controller with overcurrent fault protection
Table of Contents

Advertisement

3.3
f
unctions of inDicator leDs
Description of LEDs
Table 5
LED
RUN
STATUS
ALARM
DI
ON / OVER-TEMP
The state of the LEDs matches the corresponding parameter, except in the following special cases:
- LED 1 (green) + LED 2 (yellow) both flashing rapidly: autobaud in progress
- LED 2 (yellow) flashing rapidly: SSR temperature sensor broken or SSR Over Heat or Rotation Error
or Load_short_protection
3.4
c
ontrol connector
3.4.1
CONNECTOR J1
Figure 9
Connection schema J1
Figure 10
12
DESCRIPTION
Flashing during normal operation
On steadily: according to FW setting (see SW manual)
Off : during normal operation
On : according to FW setting (see SW manual)
State HB alarm output / Power Fault Alarm / Fuse Open
State digital input
.Green: SSR on control state
Yellow: ON SSR overtemperature alarm
Table 6
Table 7
PIN
1
2
3
4
5
6
7
8
9
0,2 - 2,5mm
0,25 - 2,5mm
NAME
DECRIPTION
OUT AL HB
OUT Alarm Switch (HB)
OUT_Master
Control output Slave (+7V)
GND
GND Control analog input
+ IN
+ Control analog input
+5V_POT
Output alim. potentiometer
IN_DIG
Digital input & PWM Input
24V Supply
Supply
18...32 Vac/Vdc
24V Supply
80994B_MHW_GTF-Xtra_05-2016_ENG
COLOR
green
yellow
red
yellow
green
yellow
24-14AWG
2
23-14AWG
2