3.14.6.
HB alarm threshold percentage
Address
Format
Single-
Multi-
node
node
1761
2785
737
16 bit
4833
The parameter sets the HB alarm threshold percentage of the current read in HB calibration.
min...max:
0.0...100.0
3.14.7.
CT reading in HB calibration
Address
Format
Single-
Multi-
node
node
1766
2790
742
16 bit
4838
The parameter sets the CT reading in HB calibration.
min...max:
0.0...3275.0
3.14.8.
VT reading in HB calibration
Address
Format
Single-
Multi-
node
node
1476
2500
452
16 bit
4548
The parameter sets the VT reading in HB calibration.
min...max:
0.0...999.9
3.14.9.
Ou.P power in calibration
Address
Format
Single-
Multi-
node
node
1767
2791
743
16 bit
4839
The parameter sets the Ou.P
min...max:
0.0...100.0
GPC-OP
Acronym
menu
05.04.04
M
Hb.P
05.05.04
E1
05.06.04
E2
GPC-OP
Acronym
menu
05.04.05
M
05.05.05
Hb.tA
E1
05.06.05
E2
GPC-OP
Acronym
menu
05.04.06
M
05.05.06
Hb.tV
E1
05.06.06
E2
GPC-OP
Acronym
menu
05.04.07
M
05.05.07
Hb.Pw
E1
05.06.07
E2
power in HB calibration.
81901A "MSW_GPC-40/600A"_03-2021_ENG_page 65
GF_eXpress menu
Description
MainMenu → M → Alarms →
HB alarm → Hb.P_1
MainMenu → E1 → Alarms →
HB alarm → Hb.P_2
MainMenu → E2 → Alarms →
HB alarm → Hb.P_3
GF_eXpress menu
Description
MainMenu → M → Alarms →
HB alarm → Hb.tA_1
MainMenu → E1 → Alarms →
HB alarm → Hb.tA_2
MainMenu → E2 → Alarms →
HB alarm → Hb.tA_3
GF_eXpress menu
Description
MainMenu → M → Alarms →
HB alarm → Hb.tV_1
MainMenu → E1 → Alarms →
HB alarm → Hb.tV_2
MainMenu → E2 → Alarms →
HB alarm → Hb.tV_3
GF_eXpress menu
Description
MainMenu → M → Alarms →
HB alarm → Hb.Pw_1
MainMenu → E1 → Alarms →
HB alarm → Hb.Pw_2
MainMenu → E2 → Alarms →
HB alarm → Hb.Pw_3
Float
■
R/W
%
(####.#)
Float
■
R/W
A
(####.#)
Float
■
R/W
V
(####.#)
Float
■
R/W
%
(####.#)
80.0
0.0
0.0
0.0