Using Digital Input 1 To Enable Software Startup - gefran GPC Configuration And Programming Manual

Advanced power controller
Table of Contents

Advertisement

4.3.

Using digital input 1 to enable software startup

Software startup (ON) can be configured with the dual
enabling condition by digital input and by writing via serial.
Enabling by digital input 1 (dIG.1) is common to all mod-
ules, while enabling by writing via serial is specific to each
individual module.
The software startup function (OFF) can be used in fault
or emergency conditions by resetting the control of the
heating resistors.
DIGITAL INPUT 1
SERIAL WRITING
ON/OFF GPC-M
SERIAL WRITING
GPC-E1 ON/OFF
SERIAL WRITING
GPC-E2 ON/OFF
ON
OFF
STATUS
ON
OFF
ON
OFF
ON
OFF
81901A "MSW_GPC-40/600A"_03-2021_ENG_page 137
Software ON/
OFF
AND
logical
AND
logical
AND
logical
Setting
Address for serial writing
dIG.1
16-bit access
STATUS_W
6
305, bit 3
ON/OFF STATUS
GPC-M
ON/OFF STATUS
GPC-E1
ON/OFF STATUS
GPC-E2
1-bit access
BIT_SOFT-
WARE_ON_
OFF
11