Address
GPC-OP
Format
Single-
Multi-
node
node
The parameter sets the alarm type for generic alarms AL1...AL8 of modules GPC-M, GPC-E1 and GPC-E2. The alarm and module con-
cerned depend on the address used.
Options:
Index
Increasing the index by a fixed amount results in the following behaviours:
Index +8
= The alarm is disabled from startup until the alarm threshold is first intercepted.
Index +16
= Alarm memory is enabled.
Index +32
= A1.t becomes the alarm activation delay time (0...999 minutes)
This does not apply to the symmetrical absolute.
Index +64
= A1.t becomes the alarm activation delay time (0...999 seconds).
This does not apply to the symmetrical absolute.
Index +128
= Alarm is disabled during softstart.
Notes:
*)
Setting not available for generic alarm 1.
The relative alarm type refers to the immediately preceding absolute alarm with index 1...8.
Examples:
Setting 20 (= 4 + 16) provides a direct, absolute and symmetrical alarm that is only enabled when the alarm threshold is exceeded for the
first time since startup.
If AL1 and AL2 are absolute, by setting AL3 as relative, alarm 3 will be relative to alarm 2.
Acronym
menu
Direct (maximum) or
Reverse (minimum)
0
Direct
1
Reverse
2
Direct
3
Reverse
4
Direct
5
Reverse
6
Direct
7
Reverse
81901 "MSW_GPC-40/600A"_03-2021_ENG_page 50
GF_eXpress menu
Description
Normal or Symmetri-
Absolute or Relative
Absolute
Absolute
Relative *
Relative *
Absolute
Absolute
Relative *
Relative *
cal (window)
Normal
Normal
Normal
Normal
Symmetrical
Symmetrical
Symmetrical
Symmetrical