3.14.3.

Delay time for HB alarm activation

Address
Format
Single-
Multi-
node
node
1080
2104
56
16 bit
4152
The parameter sets the delay time before the HB alarm is activated. The Hb.t value must be greater than the cycle time of the output with
which the HB alarm is associated.
min...max:
0...999
3.14.4.

Enabling calibration

Address
Format
Single-
Multi-
node
node
1136
2160
112
bit
4208
This bit enables the alarm threshold calibration function for modules GPC-M, GPC-E1 and GPC-E2, depending on the address used.
It should be noted that with a three-phase load, a different value can be set for the A.Hb alarm thresholds. In this mode an unbalanced
three-phase load can be controlled without problems.
Options:
OFF
= Calibration not enabled
ON
= Calibration enabled
3.14.5.

HB alarm threshold

Address
Format
Single-
Multi-
node
node
1079
2103
55
16 bit
4151
The parameter sets the HB alarm threshold.
0.0...3275.0
min...max:
GPC-OP
Acronym
menu
05.04.02
M
Hb.t
05.05.02
E1
05.06.02
E2
GPC-OP
Acronym
menu
12.01.05
M
BIT_
12.02.05
CALIB_
E1
HB
12.03.05
E2
GPC-OP
Acronym
menu
05.04.03
M
05.05.03
A.Hb
E1
05.06.03
E2
81901 "MSW_GPC-40/600A"_03-2021_ENG_page 64
GF_eXpress menu
Description
MainMenu → M → Alarms →
HB alarm → Hb.t_1
MainMenu → E1 → Alarms →
HB alarm → Hb.t_2
MainMenu → M → Alarms →
HB alarm → Hb.t_3
GF_eXpress menu
Description
MainMenu → M → Expert →
Bit → BIT_CALIB_HB_1
MainMenu → E1 → Expert →
Bit → BIT_CALIB_HB_2
MainMenu → E2 → Expert →
Bit → BIT_CALIB_HB_3
GF_eXpress menu
Description
MainMenu → M → Alarms →
HB alarm → A.Hb_1
MainMenu → E1 → Alarms →
HB alarm → A.Hb_2
MainMenu → E2 → Alarms →
HB alarm → A.Hb_3
Unsigned
R/W
sec.
Short
R/W
Float
R/W
A
(####.#)
5
0
10.0