Jumper / Dip Switch Status; Enabling Virtual Dip Switch Control - gefran GPC Configuration And Programming Manual

Advanced power controller
Table of Contents

Advertisement

3.35.9.

Jumper / DIP switch status

Address
Format
Single-
Multi-
node
node
1370
346
16 bit
The register shows the status of the jumpers / DIP switches. The status of the individual jumper / DIP switch can determine a specific
configuration.
The combination of the status of jumpers / DIP switches S7-1, S7-2, S7-3 and S7-4 determines the operating mode.
Options:
bit
0
1
2
3
4
5
6
7
8
S7-1
S7-2
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
OFF
ON
OFF
ON
OFF
3.35.10.

Enabling virtual DIP switch control

Address
Format
Single-
Multi-
node
node
1797
773
16 bit
The factory configuration has the hardware DIP switch control active (J.Set = 0). Setting parameter J.Set = 1 enables the control of virtual
DIP switches via serial.
When virtual control is active, the configuration considered is not that described by the hardware DIP switches but that shown in the J.SEr
parameter (for the writing of J.SEr refer to the table in paragraph "3.35.9. Jumper / DIP switch status").
The S7 hardware DIP switches in positions 1-2-3-4-5-7 are no longer considered while the S7 hardware DIP switch in position 6 (forced
CGF) if active (ON) has priority over the virtual DIP switches, returning the parameters J.Set and J.Ser to zero after a restart.
NOTE: Any change in the hardware DIP-Switches and J.Set and J.Ser parameters will only be active after a restart.
NOTE: As with control of hardware DIP-Switches, also for virtual control, following a change in the configuration, the parameter initial-
isation procedure must be performed after a configuration change by setting the virtual DIP-Switch position 6 (forced CGF) to ON and
restarting the product.
Options:
0
= Hardware DIP switch priority
1
= Virtual DIP switch priority (from serial line)
GPC-OP
Acronym
menu
JUMPER_
02.07
Global
STATUS
Jumper /
DIP switch
S1
S2
S7-1
S7-2
S7-3
S7-4
S7-5
Resistive load
S7-6
S7-7
Single-node mode
DIP switch status S7-1...S7-4
S7-3
S7-4
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
GPC-OP
Acronym
menu
03.01.06
J.Set
Global
81901 "MSW_GPC-40/600A"_03-2021_ENG_page 128
GF_eXpress menu
Description
MainMenu → Global → Info →
JUMPER_STATUS
Configuration
Status OFF
see table DIP switch status S7-1...S7-4
Inductive load
Default parameter configuration
Multi-node mode
Operating modes
3 single-phase loads
3 independent single-phase open delta loads
three-phase open delta/star load with neutral
three-phase closed delta load
three-phase star load without neutral
three-phase star load without neutral with TWO-PHASE control
three-phase closed delta load with TWO-PHASE control
GF_eXpress menu
Description
MainMenu → Global → Parameters →
J.Set
Unsigned
R
Short
Status ON
Unsigned
R/W
Short
0
0