3.20.6.

Analog output value

Address
Format
Single-
Multi-
node
node
1901
877
16 bit
1902
878
16 bit
1903
879
16 bit
The parameter shows the percentage value of analog outputs 1, 2 and 3, depending on the address used.

3.21. Controls - general description

The Advanced Power Controller allows control of power
output in automatic (AUTO) or manual (MAN) mode. In man-
ual mode, the control output is set to a constant value that
can be modified via serial communication.
When switching from MAN to AUTO, the setting of the
output gradient(G.Out_x) will move the Power Controller
from the current MAN setting to the new Reference Power
(SPU_x) setting.
When switching from AUTO to MAN it is possible to see a
sudden output change in power.
GPC-OP
Acronym
menu
01.01.11 Out.A01 Global
01.01.12 Out.A02 Global
01.01.13 Out.A03 Global
81901A "MSW_GPC-40/600A"_03-2021_ENG_page 97
GF_eXpress menu
Description
MainMenu → Global →
Status → OUT.A01
MainMenu → Global →
Status → OUT.A02
MainMenu → Global →
Status → OUT.A03
In manual mode, the power output can be automatically cor-
rected in relation to the reference mains voltage (riF). The%
value of the correction (Cor) is freely adjustable and acts in
an inversely proportional manner, i.e., if the reference voltage
increases, the power output decreases, and vice versa.
The following functional diagram shows the parameter pro-
cessing sequence in power output management.
Float
R
%
(####.#
Float
R
%
(####.#
Float
R
%
(####.#