Power Output Percentage; Output Power Offset; Control Output Gradient; Minimum Trigger Output - gefran GPC Configuration And Programming Manual

Advanced power controller
Table of Contents

Advertisement

3.21.4.

Power output percentage

Address
Format
Single-
Multi-
node
node
1789
2813
765
16 bit
4861
The parameter sets the percentage of the output power.
min...max: 0.0...100.0
3.21.5.

Output power offset

Address
Format
Single-
Multi-
node
node
1790
2814
766
16 bit
4862
The parameter sets the offset percentage of the output power.
min...max: -100.0...100.0
3.21.6.

Control output gradient

Address
Format
Single-
Multi-
node
node
1787
2811
763
16 bit
4859
The parameter sets the gradient for the control output, i.e., how quickly the final value is reached. The gradient is defined as a percentage
increment per second in relation to the final value to be achieved. Set the parameter to 0 to disable the gradient.
min...max: 0.0...200.0
Example: By setting the gradient to 50%/s the Ou.P output is not implemented instantaneously but gradually. If the power goes from 0%
to 100%, actuation occurs in a linear ramp of 2 seconds duration.
3.21.7.

Minimum trigger output

Address
Format
Single-
Multi-
node
node
1788
2812
764
16 bit
4860
The parameter sets the minimum output for triggering as a percentage of the maximum achievable value.
min...max: 0.0...50.0
GPC-OP
Acronym
menu
07.02.03
M
P.PEr
07.03.03
E1
01.04.03
E2
GPC-OP
Acronym
menu
07.02.04
M
P.oFS
07.03.04
E1
01.04.04
E2
GPC-OP
Acronym
menu
07.02.05
M
G.Out
07.03.05
E1
01.04.05
E2
GPC-OP
Acronym
menu
07.02.06
M
Lo.P
07.03.06
E1
01.04.06
E2
81901 "MSW_GPC-40/600A"_03-2021_ENG_page 100
GF_eXpress menu
Description
MainMenu → M → Controls → P.PEr_1
MainMenu → E1 → Controls → P.PEr_2
MainMenu → E2 → Controls → P.PEr_3
GF_eXpress menu
Description
MainMenu → M → Controls → P.oFS_1
MainMenu → E1 → Controls → P.oFS_2
MainMenu → E2 → Controls → P.oFS_3
GF_eXpress menu
Description
MainMenu → M → Controls → G.Out_1
MainMenu → E1 → Controls → G.Out_2
MainMenu → E2 → Controls → G.Out_3
GF_eXpress menu
Description
MainMenu → M → Controls → Lo.P_1
MainMenu → E1 → Controls → Lo.P_2
MainMenu → E2 → Controls → Lo.P_3
Float
R/W
%
(####.#)
Float
R/W
%
(####.#)
Float
R/W
%/s
(####.#)
Float
R/W
%
(####.#)
100.0
0.0
0.0
0.0

Advertisement

Table of Contents
loading

Table of Contents