9 TROUBLE SHOOTING
Error
Error name
code
070Ch
Disk full
Read start position
070Dh
fault
070Eh
Read range fault
070Fh
File access error
07A0h
System error
FTP server setting file
0800h
error
Incorrect FTP transfer
0801h
destination No. error
FTP transfer
0802h
destination No. non-
setting error
0803h
FTP file transfer error
9 - 38
Error definition
The disk has run out of a free
area.
The read start position is beyond
the file capacity.
The read range is not within the
file.
An error occurred when access
was made to the file.
The FTP setting file is missing or
destroyed.
The FTP transfer destination No.
is outside the setting range.
A file send request was issued to
the FTP transfer destination No.
that has not been set in the FTP
setting.
An error occurred during FTP file
transfer or the file of the transfer
source is missing.
(From the previous page)
Corrective action
 Delete unnecessary files.
 Replace the CF card.
 Check the argument of the read
start position.
 Check whether the read start
position + number of read points
fall within the file range.
 Check whether the access target
file was deleted by external FTP,
etc. during execution of the
instruction.
 System error ( 1)
 After initializing the module (refer
to Section 4.13), perform the
FTP setting (refer to Section
6.7.3) again.
 Check the FTP transfer
destination No. of the logging
setting (refer to Section 6.4.4) or
dedicated instruction (refer to
Section 8.3, 8.4).
 Check the FTP transfer
destination No. of the logging
setting (refer to Section 6.4.4) or
dedicated instruction (refer to
Section 8.3, 8.4).
 Check the FTP setting.
(Refer to Section 6.7.3)
 Check the FTP setting.
(Refer to Section 6.7.3.)
 Check the connection status with
the FTP server.
 Check the FTP server status of
the transfer destination.
 Check the transmission file
specified in the dedicated
instruction.
(Refer to Section 8.3, 8.4.)
 Check whether the transfer
source file is deleted.
 Check the logging setting.
(Refer to Section 6.7.6 (3).)
(Continued on the next page)
MELSEC-Q
Error type
Display
Display
Display
Display
Display
Stop
Continue
Continue
Continue
9 - 38